Automatic Transfer Switches for Power Source Changeover · Technical Explainer
Three-Position Changeover Switches: Checking the Motor Sequence

Separate the requested position from the achieved position
A panel controller sends a request to move a motorised changeover switch to source II. The command appears in its event log, but the receiving load position has not yet been confirmed. Treating that request as a completed transfer hides the distinction between a control instruction, actuator movement and position evidence.
A motorised changeover switch I/off/II interlock sequence needs an exact-model interface record. Keep the requested position, command acceptance conditions, movement indications and achieved-position feedback separate. A three-position description alone supplies neither a control terminal map nor a reliable transition truth table.
This guide helps transfer-panel designers and OEM control engineers prepare that record. It does not provide a wiring diagram, energization procedure or universal controller program. Its deliverable is an evidence table that the selected switch's documentation can complete before an engineering team accepts the proposed command and feedback arrangement.
Start with the ATS-M public information boundary
Den RITOKS ATS-M motorised changeover family describes source I, off and source II positions. Its public selection notes ask buyers to confirm pole count, control mode and transition timing. Those descriptions identify the commercial architecture, not the complete operating interface for a particular ordered configuration.
The public page does not establish a control pinout, pulse duration, command precedence or auxiliary-contact state table. Do not infer those details from an illustration or another manufacturer's terminals. An exact-model manual and accessory list must establish the actual control and position-feedback interfaces supplied with the order.
Keep switch identity and controller identity together. A controller specification cannot silently stand in for the motorised switch's input requirements, and a switch family page cannot establish how the proposed controller handles unsuccessful movement. The review must cover the selected combination without inventing a compatibility declaration.
The same evidence boundary applies to switching mode. Three named positions are not a declaration of closed-transition operation, source paralleling, bypass operation or an accepted isolation procedure. This article focuses on command and feedback evidence, leaving those different functional claims to their own applicable documentation.
Use manufacturer examples as documentary examples only
The motorisation-interface section of SOCOMEC's ATyS p manual identifies position-order inputs and separate position indication outputs. Its product-specific interface shows why a command and position feedback should not be treated as the same signal. No SOCOMEC terminal assignment is transferred to ATS-M here.
SOCOMEC's ATyS M auxiliary-contact page describes position signalling and offers different common arrangements. That is evidence about its own accessory offering. It does not prove which accessories are included with an ATS-M order or that two manufacturers' auxiliary circuits are interchangeable.
Use these examples to formulate questions, not to fill missing cells with borrowed values. Ask for the selected model's input characteristics, indication arrangement, accessory references and document revision. Differences in interface design may be legitimate, but the purchaser needs the actual declaration rather than a familiar-looking substitute.
Establish how a position request is accepted
Record what the exact switch calls each command and what conditions allow it to act on that command. The relevant document may distinguish operating modes, enable conditions, a stop or off request and other interface functions. Keep the manufacturer's definitions rather than inventing one universal control vocabulary.
Ask whether an input is a maintained request or an impulse and obtain its declared requirements. Do not prescribe a pulse width from a different switch. Similarly, retain the actual input supply and contact characteristics instead of assuming that a dry-contact drawing or a controller voltage label establishes compatibility.
Command precedence also needs explicit evidence. If more than one request can exist, the designer must know the documented response of the selected device and the intended controller behavior. This article does not decide which request wins, whether one overrides another or how simultaneous requests should be wired.
Record the distinction between a controller issuing an instruction and the switch accepting it. A control log can establish the first event without proving the second. Where acceptance is not independently indicated, say how the engineering review intends to establish the relevant state rather than naming an imaginary acknowledgement signal.
Treat movement as its own evidence state
An actuator can be moving while a requested destination has not yet been reached. The interface record should identify what the manufacturer actually reports during that interval. Do not derive motor status from a position-order output merely because the order remains present.
Keep the meaning of an off indication explicit. A declared position indication, a motor-available signal and the absence of two source indications are not automatically identical observations. The selected documentation must define which signal represents a position and which represents availability or another condition.
Do not fabricate an in-transition contact pattern. Depending on the actual interface, some required information may not be available as a distinct external signal. An unresolved table cell is a useful engineering question; it is not permission to assume that an unasserted contact proves the switch is stationary or isolated.
Timing deserves the same separation. Distinguish the input requirement, motion interval, intended intermediate-position interval and feedback acceptance criterion if those are relevant to the design. Obtain the actual documented values and scope. No common interval or maximum movement time is assigned to ATS-M in this guide.
Build the command, movement and feedback record
The following original worksheet is a documentary tool, not an ATS-M contact truth table. Each row describes a review situation. Complete it with selected-model evidence; do not convert the headings into terminal labels or a controller operating sequence.
| Review situation | Command information needed | Feedback information needed | Unresolved claim to avoid |
|---|---|---|---|
| Request source I | Accepted order and applicable mode conditions | Declared evidence of achieved source-I position | Assuming a logged request proves position |
| Request off | Meaning and acceptance conditions of the off request | Actual definition of off-position indication | Equating every absent source signal with off |
| Request source II | Accepted order and applicable mode conditions | Declared evidence of achieved source-II position | Treating the request as completed transfer |
| Movement not complete | Documented command state and applicable timing | Defined movement or unsettled indication, if supplied | Inventing an auxiliary-contact pattern |
| Command and observation disagree | Accepted instruction and relevant context | Actual observed signals and their definitions | Issuing an undocumented automatic retry |
| Control supply or mode changes | Documented command handling in that condition | Meaning of available position and status evidence | Assuming every signal remains authoritative |
A conceptual review case illustrates the difference. A controller record says source II was requested, while the associated position record still reports source I. The first task is to establish what each record means and whether their timestamps and state definitions are comparable. The example does not identify a fault cause or authorize another command.
In a different documentary case, a quotation mentions auxiliary contacts but does not state which positions they indicate or whether the required common arrangement is supplied. Resolve the accessory identity and signal definitions before accepting the control interface. A generic accessory description is not a completed feedback specification.

Keep interlocking separate from indication
Ask for the selected switch's mechanical and electrical interlocking description, where applicable. A physical position arrangement and an auxiliary indication serve different documentary purposes. A feedback signal should not be advertised as a verified interlock merely because it is used by a controller.
Likewise, a software command rule is not evidence of a particular mechanical interlock. The engineering record should identify which function belongs to the switch mechanism, which belongs to an external circuit and which belongs to controller logic. Do not combine all three under an unexplained “interlocked” quotation note.
Request the applicable evidence and limitations for each claimed function. This guide supplies no interlock circuit, safety-integrity claim or declaration that an auxiliary contact proves power-contact condition under every failure mode. Such claims need their own exact-product and system evidence rather than a three-position label.

Document disagreement without inventing a recovery routine
The agreed design needs a documented interpretation when the requested and indicated positions do not align. Ask the responsible engineer to define what information the controller records and how that condition enters the approved review or response concept. The purchaser should not guess an automatic corrective action.
Keep loss of control supply, mode selection and an unavailable actuator distinct where the actual documentation makes those distinctions. Do not assume that one status label covers them all. The evidence request should expose the selected interface's limitations without alleging that an unknown capability is absent hardware.
A delay or disagreement alone does not establish a welded contact, failed motor, incorrect source or faulty auxiliary device. Diagnostic conclusions require appropriate observations and qualified investigation. This article limits itself to specifying the evidence to collect and the boundaries of the claims the documents can support.
Close the procurement record with the exact interface
For an ATS-M inquiry, identify the required pole format, selected switch reference, motor/control arrangement and proposed controller. Request the exact interface manual, command requirements, position-indication definitions, included auxiliary references, mode behavior, relevant timing and interlocking evidence.
Retain revision-controlled documents with the accepted configuration. If a switch, controller or auxiliary accessory changes, revisit the affected command and feedback cells instead of carrying the former arrangement forward unchanged. The useful handoff distinguishes a requested destination, the documented transition state and the evidence for achieved position, with unresolved details visible to the engineering team.
Source notes
Sources inspected 1 October 2026. The worksheet and disagreement examples are original documentary tools, not operating instructions or an actual ATS-M signal truth table.
- RITOKS ATS-M: public source-I/off/source-II architecture and selected-model confirmation boundary.
- SOCOMEC ATyS p manual, motorisation module interface section 7.3.2: official search extraction of separate position orders and auxiliary position outputs; complete large PDF not obtained in this review. No pinout or timing transferred.
- SOCOMEC ATyS M auxiliary contacts: actual public HTML position-signalling and accessory-common descriptions. No accessory compatibility claim for ATS-M.