{"id":1785,"date":"2026-09-27T06:34:01","date_gmt":"2026-09-27T06:34:01","guid":{"rendered":"https:\/\/ritoks.com\/?p=1785"},"modified":"2026-10-04T06:58:11","modified_gmt":"2026-10-04T06:58:11","slug":"2-pole-vs-4-pole-dc-circuit-breakers","status":"publish","type":"post","link":"https:\/\/ritoks.com\/da\/2-pole-vs-4-pole-dc-circuit-breakers\/","title":{"rendered":"2-polede kontra 4-polede j\u00e6vnstr\u00f8msafbrydere: Opbygning og valgkriterier"},"content":{"rendered":"<p class=\"wp-block-paragraph\">Two-pole and four-pole DC circuit breakers are not simply small and large versions of the same answer. Pole count affects the permitted connection path, how conductors are disconnected and sometimes the voltage at which the complete device has documented interruption capability. The correct arrangement depends on system earthing, voltage, fault-current direction and the manufacturer&#8217;s exact wiring diagram.<\/p>\n<p class=\"wp-block-paragraph\">Denne sammenligning udg\u00f8r et sp\u00f8rgsm\u00e5lsgrundlag for k\u00f8bere af j\u00e6vnstr\u00f8ms-afbrydere (DC MCB). Den antyder ikke, at fire poler automatisk er sikrere, eller at to poler altid er tilstr\u00e6kkelige. Nominel v\u00e6rdi og tilslutningsoplysninger skal vedr\u00f8re den foresl\u00e5ede bestillingskode, ikke et tilst\u00f8dende produkt i kataloget.<\/p>\n<h2 class=\"wp-block-heading\">Man skal f\u00f8rst skelne mellem ledere og afbryderpoler<\/h2>\n<p class=\"wp-block-paragraph\">Et to-leder-j\u00e6vnstr\u00f8mssystem har en positiv og en negativ leder, men dette alene er ikke afg\u00f8rende for, hvor mange poler afbryderen skal have. En producent kan angive, at der skal tilsluttes mere end \u00e9n pol i serie langs den ene leder for at opn\u00e5 en bestemt nominel j\u00e6vnstr\u00f8mssp\u00e6nding. I en anden opstilling kan der anvendes poler i begge ledere. Det er tegningen, ikke ordet \u201cfirepolet\u201d, der fastl\u00e6gger, hvad der rent faktisk afbrydes.<\/p>\n<p class=\"wp-block-paragraph\">P\u00e5 projektets enkeltlinje skal du markere alle ledere, kilde- og forbrugsforbindelser. Tegn derefter den foresl\u00e5ede str\u00f8mvej gennem hver pol. Hvis der er behov for en broforbindelse, skal du angive, om der er tale om et producentgodkendt tilbeh\u00f8r, en medf\u00f8lgende forbindelse eller en forbudt \u00e6ndring udf\u00f8rt p\u00e5 stedet. Medregn ikke eksterne klemmer, og g\u00e5 ud fra, at hver klemme svarer til en uafh\u00e6ngigt afsk\u00e6rmet leder.<\/p>\n<p class=\"wp-block-paragraph\">Sp\u00f8rg, om afbryderen er beregnet til at afbryde \u00e9n polaritet, begge polariteter eller en bestemt seriekobling. Systemets jordforbindelse og fejlscenarier har indflydelse p\u00e5 denne beslutning. Et system med jordede ledere kan vurderes anderledes end et isoleret system; ingeni\u00f8ren skal anvende de relevante installationsregler og fejlanalyser.<\/p>\n<h2 class=\"wp-block-heading\">Sammenlign den n\u00f8jagtige nominelle j\u00e6vnsp\u00e6nding<\/h2>\n<p class=\"wp-block-paragraph\">DC arcs do not have the natural current zero crossings of AC. Product-specific pole arrangements may therefore be used to manage interruption at higher DC voltages. Schneider Electric&#8217;s DC breaker guides show that voltage limits can depend on series-pole connections and system topology. Those examples are for Schneider products, not a universal conversion formula.<\/p>\n<p class=\"wp-block-paragraph\">Obtain the maximum operating voltage at the installation point, including charging or other high-voltage states. Compare it with the candidate&#8217;s rated DC operational voltage for the exact number of poles and connection drawing. Do not use a headline voltage from a four-pole variant to approve a two-pole variant, or vice versa.<\/p>\n<p class=\"wp-block-paragraph\">If a supplier proposes extra poles in series, request the diagram showing terminal order, polarity and links. The higher voltage claim must be explicitly documented for that exact arrangement. A user-created series bridge based on a competitor&#8217;s drawing is not evidence that the new breaker will interrupt correctly.<\/p>\n<figure data-spectra-id=\"spectra-31125f65-ab0b-4101-a54e-663be5093185\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" height=\"1050\" width=\"1400\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1.webp\" alt=\"Diagrammer over ledere og seriekoblingsveje for to-polede og fire-polede j\u00e6vnstr\u00f8msafbrydere\" class=\"wp-image-1787\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">Antallet af poler skal omregnes til en dokumenteret leder- og seriepol-forl\u00f8b.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">Kontroller den forventede fejlstr\u00f8m ved samme sp\u00e6ndingsgrundlag<\/h2>\n<p class=\"wp-block-paragraph\">A breaker must interrupt the fault available at its terminals. Provide the location-specific prospective DC fault current, not only the source&#8217;s nominal current. Batteries, converters, parallel strings and other feeds may change the duty. Compare the result with the exact candidate&#8217;s published DC breaking capacity at the relevant voltage and pole connection.<\/p>\n<p class=\"wp-block-paragraph\">The current rating and breaking capacity are different specifications. More poles do not automatically create a higher fault-current rating, and a product&#8217;s AC interrupting data cannot stand in for DC data. Ask the supplier to identify the rating table and test conditions that support the proposed connection.<\/p>\n<p class=\"wp-block-paragraph\">S\u00f8rg for, at eventuelle antagelser om kildebidrag og jordforbindelse fremg\u00e5r tydeligt. Hvis en fejlunders\u00f8gelse ikke er afsluttet, skal sammenligningen af afbrydere angives som forel\u00f8big. Indk\u00f8bsafdelingen kan s\u00f8ge efter relevante dokumenter, mens ingeni\u00f8rafdelingen f\u00e6rdigg\u00f8r beregningen af den tilg\u00e6ngelige fejlstr\u00f8m.<\/p>\n<h2 class=\"wp-block-heading\">Gennemg\u00e5 de g\u00e6ldende regler for retning og polaritet<\/h2>\n<p class=\"wp-block-paragraph\">Nogle j\u00e6vnstr\u00f8msbeskyttelsesanordninger stiller krav til polaritet (kilde\/belastning eller plus\/minus). Et system med batteriopladning og -afladning kan have normal str\u00f8m i mere end \u00e9n retning, og fejlstr\u00f8mmen kan f\u00f8lge en helt tredje vej. Selv om anordningen er firpolet, er det stadig n\u00f8dvendigt at l\u00e6se polaritetsmarkeringerne og monteringsvejledningen.<\/p>\n<p class=\"wp-block-paragraph\">For hver drifts- og fejltilstand skal det fremg\u00e5, hvilken terminal der er under sp\u00e6nding, og hvordan str\u00f8mmen n\u00e5r frem til enheden. Sammenlign dette med producentens pr\u00e6cise tegning. Hvis den foresl\u00e5ede afbryder beskrives som ikke-polariseret, skal omfanget af denne angivelse bekr\u00e6ftes ved den kr\u00e6vede sp\u00e6nding og afbrydelseskapacitet; dette m\u00e5 ikke fortolkes som ubegr\u00e6nset tovejsfunktion.<\/p>\n<p class=\"wp-block-paragraph\">Hvis tegningen giver anledning til tvivl, skal du bede leverand\u00f8ren om en skriftlig afklaring, der henviser til ordrekoden. Du m\u00e5 ikke afklare tvetydige markeringer ved at pr\u00f8ve at tilslutte ledningerne. En forkert retning er muligvis ikke tydelig under normal drift, men kan have betydning i tilf\u00e6lde af en fejl.<\/p>\n<h2 class=\"wp-block-heading\">Overvej behovene for isolering og vedligeholdelse<\/h2>\n<p class=\"wp-block-paragraph\">Angiv, hvilke ledere der skal afbrydes i forbindelse med den p\u00e5t\u00e6nkte vedligeholdelse eller isoleringsfunktion. En sikringsafbryder og en afbryder-afkobler kan have forskellige godkendte funktioner. Kontroller, om den p\u00e5g\u00e6ldende enhed er klassificeret til den p\u00e5t\u00e6nkte isoleringsfunktion, og hvad der forbliver under sp\u00e6nding efter \u00e5bning i den foresl\u00e5ede polkonfiguration.<\/p>\n<p class=\"wp-block-paragraph\">Tavlebyggere b\u00f8r m\u00e6rke begge sider af enheden og tydeligt angive forbindelserne p\u00e5 f\u00e6rdigtegningerne. En firepolet enhed, hvor der er to poler i serie pr. polaritet, kr\u00e6ver ikke samme vedligeholdelse som fire uafh\u00e6ngige ledere. Kabinettet og afsp\u00e6rringsproceduren skal afspejle den faktiske topologi.<\/p>\n<h2 class=\"wp-block-heading\">Sammenlign to-polede og fire-polede kandidater p\u00e5 en retf\u00e6rdig m\u00e5de<\/h2>\n<figure class=\"wp-block-table\"><table><thead><tr><th>Afg\u00f8relse<\/th><th>Tvejsidet anmeldelse<\/th><th>Anmeldelse af \u00bbFour-pole\u00ab<\/th><\/tr><\/thead><tbody><tr><td>Forbindelse<\/td><td>Hvilken leder\/bane bruger hver pol?<\/td><td>Er polerne forbundet i serie eller ligger de p\u00e5 separate baner?<\/td><\/tr><tr><td>J\u00e6vnsp\u00e6nding<\/td><td>Vurdering ved den n\u00f8jagtige ledningsf\u00f8ring<\/td><td>Vurdering ved den n\u00f8jagtige ledningsf\u00f8ring<\/td><\/tr><tr><td>Fejlbetjening<\/td><td>Data for j\u00e6vnstr\u00f8msafbrydelse ved den p\u00e5g\u00e6ldende sp\u00e6nding<\/td><td>Data for j\u00e6vnstr\u00f8msafbrydelse ved den p\u00e5g\u00e6ldende sp\u00e6nding<\/td><\/tr><tr><td>Retning<\/td><td>Anvisninger vedr\u00f8rende terminaler og polaritet<\/td><td>Anvisninger vedr\u00f8rende terminaler og polaritet<\/td><\/tr><tr><td>Isolation<\/td><td>Hvilke ledere \u00e5bner?<\/td><td>Hvilke ledere \u00e5bner?<\/td><\/tr><\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">Undlad at udfylde tabellen med generiske antagelser som \u201c2P\u201d og \u201c4P\u201d. Indtast ordrekoder og dokumentrevisioner. Hvis kandidaterne underst\u00f8tter forskellige forbindelsestopologier, skal du forklare dette tydeligt i stedet for at fremstille den ene som en direkte opgradering.<\/p>\n<figure data-spectra-id=\"spectra-45648828-6c52-42b5-894a-4c25b9b9a97a\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" height=\"1050\" width=\"1400\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1.webp\" alt=\"Bevismatrix for to- og firepolet j\u00e6vnsp\u00e6nding, afbrydelseskapacitet og isolering\" class=\"wp-image-1788\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">Sammenlign data om sp\u00e6nding og afbrydelser for den n\u00f8jagtige model, ikke blot antallet af master.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">Konsekvenser for plads, varmeforhold og ledningsf\u00f8ring<\/h2>\n<p class=\"wp-block-paragraph\">Fire poler kr\u00e6ver generelt st\u00f8rre fysisk bredde og kan kr\u00e6ve flere forbindelser eller ledningsf\u00f8ring, men de faktiske dimensioner fremg\u00e5r af produkttegningen. Flere str\u00f8mf\u00f8rende elementer kan ogs\u00e5 p\u00e5virke varmeafledningen; producenten kan angive specifikke krav til neddimensionering eller installation. Kontroller kabinetets temperatur, tilst\u00f8dende enheder, plads til samling af samleskinner eller kabler samt monteringsretningen.<\/p>\n<p class=\"wp-block-paragraph\">Et kompakt to-polet forslag b\u00f8r ikke v\u00e6lges udelukkende for at spare plads p\u00e5 skinnerne, hvis dets dokumenterede j\u00e6vnsp\u00e6nding eller tilslutningskapacitet er utilstr\u00e6kkelig. Tilsvarende b\u00f8r en st\u00f8rre fire-polet enhed ikke v\u00e6lges uden f\u00f8rst at have kontrolleret ledningsf\u00f8ringen og de termiske konsekvenser. Den bedste l\u00f8sning er den godkendte elektriske kredsl\u00f8bskonfiguration, der kan installeres og vedligeholdes korrekt.<\/p>\n<h2 class=\"wp-block-heading\">Dokument\u00e9r alle kilder til p\u00e5standen om vurderingen<\/h2>\n<p class=\"wp-block-paragraph\">En trov\u00e6rdig sammenligning b\u00f8r angive det n\u00f8jagtige datablade, dets revisionsnummer, den side, der indeholder tabellen over j\u00e6vnstr\u00f8msv\u00e6rdier, samt installationstegningen, der viser den tilsvarende terminalforbindelse. Opbevar disse dokumenter samlet. En nomineltabel uden tilslutningsdiagrammet eller et tilslutningsdiagram uden oplysninger om afbryderkapaciteten udg\u00f8r en v\u00e6sentlig mangel. K\u00f8bere b\u00f8r bede leverand\u00f8rerne om at angive, hvilken foresl\u00e5et ordrekode hver side d\u00e6kker.<\/p>\n<p class=\"wp-block-paragraph\">Hvis en angivet enhed har flere angivne sp\u00e6ndinger, skal det fastsl\u00e5s, om disse svarer til forskellige poltal, seriekoblingsm\u00e5der, jordforbindelsessystemer eller testbetingelser. De mest gunstige v\u00e6rdier m\u00e5 ikke sammenl\u00e6gges til en samlet specifikation. Sammenligningen skal ogs\u00e5 angive eventuelt tilbeh\u00f8r eller fabriksforbindelser, der er n\u00f8dvendige for at realisere den testede konfiguration. En lav enhedspris kan v\u00e6re vildledende, hvis der kr\u00e6ves specielle forbindelser, et st\u00f8rre kabinet eller yderligere ledningsf\u00f8ring.<\/p>\n<p class=\"wp-block-paragraph\">Ved designgennemgangen b\u00f8r en anden person end den, der har udarbejdet tegningerne, tegne den aktuelle rute op p\u00e5 begge tegninger. Denne uafh\u00e6ngige kontrol kan afsl\u00f8re en manglende bro eller en leder, der er placeret p\u00e5 den forkerte terminal, inden enheden samles. Resultatet b\u00f8r registreres som en topologikontrol, adskilt fra sp\u00e6ndings- og fejlstr\u00f8msberegningerne.<\/p>\n<h2 class=\"wp-block-heading\">Hvad skal der medtages i en sammenlignende anmodning om tilbud<\/h2>\n<p class=\"wp-block-paragraph\">Send systemoplysninger om enkeltledninger, sp\u00e6ndingskurve, jordforbindelseskonfiguration, fejlstr\u00f8msresultater, forventede str\u00f8mretninger, ledere, der skal afbrydes, samt begr\u00e6nsninger vedr\u00f8rende plads i tavlen. Bed leverand\u00f8ren om de n\u00f8jagtige bestillingskoder for to- og firepolede enheder, tabeller over j\u00e6vnstr\u00f8msv\u00e6rdier, ledningsdiagrammer, polaritetsanvisninger, afbrydelsesdata og installationskrav.<\/p>\n<p class=\"wp-block-paragraph\">Den <a href=\"https:\/\/ritoks.com\/da\/product-category\/dc-power-protection\/dc-circuit-breakers\/dc-miniature-circuit-breakers\/\">DC-afbryderkategori<\/a> giver en erhvervsm\u00e6ssig sammenh\u00e6ng. Den <a href=\"https:\/\/ritoks.com\/da\/products\/2p-dc-miniature-circuit-breaker-500-1000v-6-63a\/\">serie af to-polede j\u00e6vnstr\u00f8ms-afbrydere<\/a> og <a href=\"https:\/\/ritoks.com\/da\/products\/high-current-dc-miniature-circuit-breaker-12-125v-63-250a\/\">serien af j\u00e6vnstr\u00f8ms-MCB\u2019er til h\u00f8jere str\u00f8mstyrker<\/a> er udgangspunkter, ikke bevis for, at der findes et specifikt alternativ med fire poler, eller at nogen af dem passer til anvendelsen.<\/p>\n<p class=\"wp-block-paragraph\">Anvendelse <a href=\"https:\/\/ritoks.com\/da\/contact-us\/\">Kontakt RITOKS<\/a> for at anmode om modelspecifikke dokumenter. Hvis det foresl\u00e5ede antal master \u00e6ndrer paneltegningen, skal valget sendes tilbage til teknikafdelingen, inden der bestilles. Opbevar det endelige tilslutningsdiagram sammen med styklisten til kontrol og eventuelle fremtidige udskiftninger.<\/p>\n<h2 class=\"wp-block-heading\">Ofte stillede sp\u00f8rgsm\u00e5l<\/h2>\n<h3 class=\"wp-block-heading\">Er en firepolet j\u00e6vnstr\u00f8msafbryder altid bedre?<\/h3>\n<p class=\"wp-block-paragraph\">Nej. Den underst\u00f8tter muligvis et andet, af producenten godkendt tilslutnings- eller frakoblingsform\u00e5l, men egnetheden afh\u00e6nger af den n\u00f8jagtige sp\u00e6nding, fejlbelastning, ledningsf\u00f8ring og systemudformning.<\/p>\n<h3 class=\"wp-block-heading\">Betyder \u00bbto-polet\u00ab, at begge polariteter er beskyttet?<\/h3>\n<p class=\"wp-block-paragraph\">Ikke n\u00f8dvendigvis. Polerne kan v\u00e6re forbundet i serie p\u00e5 \u00e9n str\u00f8mvej i en dokumenteret konfiguration. L\u00e6s det p\u00e5g\u00e6ldende skema og find ud af, hvilke ledere der rent faktisk er \u00e5bne.<\/p>\n<h3 class=\"wp-block-heading\">Kan poler forbindes i feltet for at opn\u00e5 en h\u00f8jere nominel effekt?<\/h3>\n<p class=\"wp-block-paragraph\">Kun hvis den n\u00f8jagtige dokumentation fra producenten tillader tilslutningen, angiver de n\u00f8dvendige forbindelser og oplyser den deraf f\u00f8lgende nominelle ydelse. Man m\u00e5 aldrig udlede dette ud fra et andet produkt.<\/p>\n<h2 class=\"wp-block-heading\">Konklusion<\/h2>\n<p class=\"wp-block-paragraph\">Choose a DC breaker pole arrangement by mapping the system conductors and fault paths to the manufacturer&#8217;s exact connection diagram. Then verify voltage, DC breaking capacity, polarity and isolation requirements for that arrangement. Pole count is a starting question, not a rating.<\/p>\n<h2 class=\"wp-block-heading\">Referencer<\/h2>\n<ul class=\"wp-block-list\"><li><a href=\"https:\/\/library.e.abb.com\/public\/da3ed0fd2ecc4c92931126492e57e00a\/1SXU400208C0201_ABB%20MCB%20CT_DGT.pdf\" target=\"_blank\" rel=\"noopener\">ABB, S200UDC miniatureafbryder \u2013 diagrammer til j\u00e6vnstr\u00f8msanvendelse<\/a>.<\/li><li><a href=\"https:\/\/www.se.com\/us\/en\/download\/document\/CA908061E\/\" target=\"_blank\" rel=\"noopener\">Schneider Electric: Vejledning til valg af j\u00e6vnstr\u00f8msafbrydere og poltilslutning<\/a>.<\/li><li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66277\" target=\"_blank\" rel=\"noopener\">IEC, IEC 60947-2:2024 afbrydere<\/a>.<\/li><\/ul>","protected":false},"excerpt":{"rendered":"<p>Compare two- and four-pole DC breakers through conductor paths, manufacturer wiring diagrams, voltage and fault-interruption evidence.<\/p>","protected":false},"author":1,"featured_media":1786,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":"viox","ritoks_resource_product_cat_term_id":125,"footnotes":""},"categories":[64],"tags":[],"class_list":["post-1785","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-circuit-protection"],"acf":[],"spectra_blocks_featured_image_url":{"thumbnail":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-150x150.webp","width":150,"height":150},"medium":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-300x169.webp","width":300,"height":169},"medium_large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-768x432.webp","width":768,"height":432},"large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-1024x576.webp","width":1024,"height":576},"full":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1.webp","width":1600,"height":900}},"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/da\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/posts\/1785","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/comments?post=1785"}],"version-history":[{"count":2,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/posts\/1785\/revisions"}],"predecessor-version":[{"id":2157,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/posts\/1785\/revisions\/2157"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/media\/1786"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/media?parent=1785"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/categories?post=1785"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/da\/wp-json\/wp\/v2\/tags?post=1785"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}