Automatic Transfer Switches for Power Source Changeover · Technical Explainer
PC-Class ATS Short-Circuit Ratings: Reading the Required Conditions

Keep classification separate from fault-rating acceptance
A transfer-switch quotation identifies a PC-class device and a rated operating current. That information is not a complete short-circuit assessment for the distribution panel. The designer still needs the exact fault-rating declaration, its conditions and the protective arrangement required for the proposed installation.
A PC-class ATS conditional short-circuit rating and protection review should retain the selected model, voltage, duration and specified short-circuit protective device together. Classification alone is not evidence of a universal short-circuit breaking capacity. Nor can one isolated kA figure replace the supporting test configuration and conditions.
This guide helps distribution designers and project purchasers prepare a fault-evidence record. It does not choose an upstream fuse or breaker, calculate a project fault level or authorize installation. The useful deliverable identifies which rating has been declared and what evidence is still needed to match it to the actual application.
Begin with the public RITOKS evidence boundary
Yang G2R-63 II DIN-rail automatic transfer switch public page describes a PC-class transfer architecture. It explicitly omits short-circuit ratings because the available evidence is not sufficiently consistent for public use. Do not fill that gap with another manufacturer's table or interpret the operating-current choices as fault ratings.
Yang RITOKS ATS-M motorised changeover family also lists a PC-class architecture and asks for exact-model ratings and test reports. Its family description is not an accepted coordination table for every listed frame. Retain the orderable configuration and relevant documents before closing a protection claim.
Neither page establishes a universal protective-device pairing. Related products shown on a website are not short-circuit coordination evidence. The supplier must identify the actual rating and applicable conditions for the selected transfer switch rather than relying on a nearby breaker or fuse link as proof.
Use those public limitations to make the inquiry precise. Missing evidence does not prove a device lacks every fault capability, but it prevents a purchaser from advertising an unsupported value. The interim record should say “selected model; fault-rating conditions pending,” not silently substitute a family headline.
Read PC class without adding an undocumented breaking function
SOCOMEC's ATyS a M manual describes that PC-class product's assigned making and withstanding of short-circuit currents. This illustrates why classification and the particular assigned characteristics must be read together. It is not a RITOKS test report or a transferable fault rating.
Do not use a PC-class label as a shortcut to a short-circuit interruption claim. Ask what the selected equipment actually declares and which protective function belongs elsewhere in the system. The architecture label cannot supply an omitted making, withstand, conditional or breaking declaration.
Keep the applicable standard and edition with the document. A manufacturer's declaration under one framework must remain within that framework's definitions and test scope. This article does not reconstruct a complete current standard from an educational example or claim certification for a RITOKS model.
If a tender uses terminology from a different framework, identify the difference before comparing numbers. Do not simply rename a UL withstand-and-closing declaration as an IEC conditional short-circuit declaration. Request the applicable evidence for the actual requirement; similar terminology does not establish identical test conditions.
Preserve the meaning of each fault characteristic
ABB's official short-circuit definitions discussion distinguishes conditional capability supported by a short-circuit protective device from time-bounded withstand. It also explains why the relevant standard's definitions matter. Those principles guide the documentary review here, not a numeric ATS selection.
When an Icw value is supplied, retain its stated duration and voltage. A time omitted from the quotation makes the comparison incomplete. Do not treat a withstand declaration as permission to interrupt the same current, or assume that a different time gives the same declared capability.
When a making characteristic such as Icm is supplied, preserve the manufacturer's definition, waveform convention and conditions. A peak making declaration and a time-bounded rms withstand declaration are different information. This article gives no conversion factor between them and assigns no missing Icm value to either RITOKS family.
For a conditional short-circuit declaration, retain the named protective arrangement and all associated conditions. Do not compare its number as if it were an unprotected withstand value. Keep the manufacturer's symbols and terminology visible, since an isolated acronym can conceal the scope the actual document intended.
Ask which protective arrangement belongs to the declaration
Request the exact short-circuit protective device information associated with the conditional rating. Depending on the declaration, relevant details may include a device reference, characteristic, rating, settings or another specified limitation. Do not replace the supplied conditions with an apparently similar product or a matching nominal ampere value.
If the evidence identifies only a fuse-conditioned case, that does not automatically support a breaker-conditioned installation. Conversely, do not infer a fuse pairing from a table describing a particular breaker arrangement. The supplier or responsible designer must establish the applicable supported configuration.
Also retain the configuration of the transfer switch used for the evidence. Pole arrangement, exact variant and declared voltage belong in the record where relevant. A family name or a frame-size match alone cannot prove that a test covers the ordered product and installation.
No recommended protection pairing is supplied here. This guide does not prescribe a device, setting, clearing time or protection coordination outcome. It creates an evidence request that can be answered using the actual manufacturer documents and the project's protection design.
Build a rating-condition comparison record
The following original worksheet prevents a quotation's most visible number from losing its qualifiers. It is not a RITOKS rating table. Populate each field from the exact-model declaration or leave it explicitly unresolved.
| Kolom ulasan | Information to retain | Shortcut to reject |
|---|---|---|
| Equipment identity | Exact reference, variant and document revision | Assuming every frame shares the same rating |
| Framework | Applicable standard, edition and declared scope | Treating UL and IEC claims as identical |
| Tegangan | Voltage associated with the fault declaration | Using an operating-voltage headline as the test condition |
| Icw, if declared | Value, units, duration and conditions | Removing the time from the comparison |
| Icm, if declared | Making definition and associated conditions | Substituting a withstand or breaking value |
| Conditional rating | Value and full protective arrangement | Presenting it as unprotected capability |
| Specified SCPD | Exact required characteristics and limitations | Recommending a nearby product without evidence |
| Test configuration | Applicable selected configuration and report | Extending a neighboring model's test |
Consider a documentary example in which two quotations display the same kA number but only one includes the associated protective arrangement. They are not yet equivalent evidence. The incomplete quotation needs clarification before the purchaser can compare the supported capability.
In another case, a table provides a short-time withstand value but the proposed comparison omits its duration. Restore the original duration and scope rather than treating the value as timeless. The question is whether the actual document matches the project requirement, not which isolated number looks larger.

Keep the project fault requirement and product declaration distinct
The project's prospective fault conditions need their own authorized design basis. Record where the requirement applies and which source arrangement it represents. This article does not calculate those conditions from an assumed transformer or generator, and it does not prescribe a universal design fault level.
For a two-source application, do not assume one source's record establishes every relevant configuration. Ask the responsible designer which conditions must be evaluated and retain that scope in the request. A transfer function does not remove the need to understand the actual fault conditions at the installed equipment.
The product declaration then needs to be evaluated against that requirement with its conditions intact. Do not erase a specified SCPD, duration or voltage to obtain an apparently convenient match. A supported conditional arrangement must remain the arrangement described by the supporting evidence.
Keep system coordination claims separate as well. Fault-rating evidence for a component is not automatically proof of every selectivity or downstream protection outcome. Such conclusions need their own applicable design and manufacturer evidence rather than being inferred from a PC-class label.
Record changes before accepting a substitute
If purchasing proposes a different transfer-switch variant or protective device, identify which part of the rating-condition record has changed. An unchanged current headline does not demonstrate an unchanged fault declaration. The substituted configuration needs its own supported applicability review.
Retain the earlier document and the revision decision so that later reviewers can see why the arrangement was accepted or left pending. Do not silently carry a conditional rating across a changed protective arrangement. Documentary traceability matters because the omitted qualifier may be the condition that made the original claim valid.

Close the supplier inquiry with conditions attached
For G2R-63 II or ATS-M, provide the exact configuration and the project fault requirement defined by the responsible designer. Request the applicable standard/edition, model-specific fault declarations, Icw with duration, making information if assigned, conditional-rating conditions and the specified SCPD evidence.
Accept the record only within the supported scope. A useful quotation preserves the protective arrangement and test conditions instead of advertising a bare fault number. That keeps PC classification, short-time withstand, making capability and conditional protection evidence distinct without inventing a RITOKS breaking rating or recommending an unverified pairing.
Source notes
Sources inspected 1 October 2026. Worksheet and quotation cases are original documentary tools. No external fault value, protective pairing, standard certification or UL-to-IEC equivalence is transferred to RITOKS.
- RITOKS G2R-63 II: PC-class public description and explicitly omitted short-circuit claims.
- RITOKS ATS-M: selected-variant and test-report requirements.
- SOCOMEC ATyS a M manual: introduction's product-specific PC making/withstand statement, not numerical table transfer.
- ABB short-circuit definitions: qualitative conditional/SCPD and time-bounded withstand distinctions in its stated IEC contexts.