Current Transformers · Technical Explainer
CT Burden for Long Secondary Leads: What to Calculate Before Ordering
When a current transformer is installed far from its meter, cable is part of the measurement circuit. A CT's rated burden is not simply the number printed on the receiving instrument. The secondary leads, terminals, shorting or test block and every connected device contribute to the total load seen by a conventional current-output CT. If that total exceeds the selected CT's documented burden at its accuracy class, an otherwise plausible ratio may not deliver the expected performance. This guide is a buyer's calculation-input checklist, not an instruction to wire a live CT secondary.

RITOKS lists several Current Transformer families. Il BH-0.66 60I product page includes /5 A ratio rows. The DP split-core family page names frame references but requires exact secondary-output and burden confirmation. The miniature GTA20L family has yet another published output arrangement. Do not take a burden or output from one of these families and use it as the specification for another. Identify the exact CT and meter before doing even a preliminary lead assessment.
Burden Is a Circuit Total
The receiver's input is one component of the secondary burden. Secondary conductor resistance also dissipates power, and a long run can become material. Schneider Electric's CT guidance explicitly directs engineers to add instrument burden and secondary-wiring losses when determining a CT's minimum burden requirement. It suggests a larger conductor cross-section or a documented 1 A secondary as possible ways to reduce wiring losses where compatible products exist. Those options are engineering alternatives, not evidence that RITOKS offers them for every model.
At a specified secondary current, the resistive part of cable burden follows the familiar relationship between current, voltage drop and resistance: power in the loop is proportional to the square of secondary current times loop resistance. This relationship explains why both the selected secondary current and the complete return-path resistance matter. It does not replace a manufacturer's accuracy/burden table. The table may specify a permitted range, power factor, frequency or other conditions that must be respected.
An easy error is to add only the “one-way” CT-to-meter distance. Current travels through an outgoing and a returning conductor. The conductor route may also include extra loops, terminal strips and a shorting block. Record the actual two-conductor circuit length or the as-built route, not just the straight-line distance on a panel layout. The second easy error is to read a meter's current-input burden at the wrong current or model variant. Use the exact receiving device documentation.

First Confirm the CT Secondary
“Current transformer” does not automatically mean a 5 A output. Some conventional CTs have 1 A secondaries, some published families use smaller current outputs and some sensors require a different receiving interface. The RITOKS BH-0.66 60I family is a named /5 A example; the public DP page does not establish the same complete secondary configuration for every frame. The meter input must explicitly accept the exact selected CT's output and ratio.
Phoenix Contact's CT overview presents 1 A and 5 A secondary options within its own transformer range. Schneider Electric explains that, for the same wiring resistance, a 1 A secondary can have much lower lead loss than a 5 A secondary. Neither manufacturer statement proves that a specific RITOKS model is sold with a 1 A option. Ask the supplier to identify the orderable secondary and its burden/accuracy data rather than writing an unverified alternative into the purchase order.
If the installed receiver accepts only a specified input, that requirement may govern the route. Do not select a 1 A CT to reduce cable loss if the meter only accepts 5 A. A separately engineered interface change could be possible, but it must be documented and priced as a change to the entire measurement chain. A current-output CT should not be connected to an ordinary voltage-input channel because both connectors happen to fit a terminal strip.
Gather the Cable Inputs
For each candidate route, record conductor material, cross-section or gauge, actual two-way length and the cable manufacturer's resistance data at the relevant condition. Include the routing through marshalling cabinets, terminal blocks and any test or shorting links. If a meter is many meters from the CT, the cable may pass through more than one drawing sheet or cabinet; the procurement schedule should still show the complete path.
Temperature matters because conductor resistance changes. Use the project's installation conditions and the chosen cable's published data, not an unsupported ambient multiplier. Check the proposed cable's insulation, voltage and installation requirements separately from burden. A larger copper area may reduce resistance but does not automatically satisfy every mechanical or code requirement. The design authority must approve cable type and routing.
Schneider Electric's wire-length FAQ tells users to begin with the CT's rated secondary current and burden at rated accuracy, then include the distance from CT to meter and the shorting block when selecting conductor size. The page illustrates a method for its supported devices; it does not provide a universal RITOKS cable chart. Ask for project-specific calculations and exact product documents.
Gather the Instrument and Accessory Inputs
The meter's burden may be given in VA at its rated current or as an input impedance. Record the exact number, unit and stated condition. If more than one instrument is proposed on a secondary, do not simply assume all can share the loop; the total burden, connection sequence and meter manufacturer's instructions must be evaluated. Consider test switches, shorting blocks, terminal transitions and protection devices only where they are actually in the chosen secondary path.
A current-input channel's advertised compatibility with CTs does not prove a particular burden. Some instruments publish separate burdens for 1 A and 5 A inputs. For example, Schneider Electric's PM5100 specifications identify its supported CT secondary options and input burden. Those PM5100 figures are not RITOKS CT data and should not be placed in a different meter's schedule. Their value here is to show why the receiver model must be named.
For a procurement comparison, make a line-item list rather than one estimated “system VA” field. Label each source: CT rated burden, meter burden, cable resistance, accessory contribution and design margin if the project requires one. If a term is not published, mark it pending. An unverified accessory or meter input can decide the result, so a precise-looking total built from a guess is worse than an honest incomplete schedule.
Read the Accuracy Condition With the Burden
The required accuracy class belongs to a defined CT variant and measurement condition. A CT may have different performance at different ratios, burden levels or current points. Ask the supplier for the exact rated burden associated with the claimed class for the selected model, secondary and frequency. A burden rating without the associated accuracy statement may not answer a metering project's question.
Do not assume that “lower burden is always better” without reading the product's specified operating range and receiving equipment instructions. The aim is a documented compatible secondary circuit, not the smallest possible calculated number. Conversely, a measured current display that seems plausible does not prove the installation is within accuracy. The system should be reviewed against the CT and receiver documents, then tested under the project-approved procedure.
The RITOKS DP page is particularly explicit about unresolved data. It publishes a split-core family and selected accuracy information but not every exact ratio, output, burden, frequency or insulation detail. Those missing fields must be requested. The CT selection guide identifies ratio, burden and construction as separate selection questions; it cannot fill a missing model row with values from an unrelated product.
A Worked Input Template Without Invented Model Data
Prepare the calculation worksheet with blanks rather than plugging in arbitrary figures:
| Input | Source to request | Recorded value |
|---|---|---|
| Exact CT model and ratio | Supplier model row | Pending |
| Rated secondary current | Exact CT data sheet | Pending |
| Burden allowed at required accuracy | Exact CT data sheet | Pending |
| Meter input and burden | Exact meter manual | Pending |
| Two-way lead length | Route drawing or field survey | Pending |
| Cable resistance | Cable manufacturer's data | Pending |
| Shorting/test and terminal contributions | Installed accessory data | Pending |
| Final assessment | Responsible design authority | Pending |

Once the values are available, the engineer can calculate cable resistance and secondary wiring loss at the correct rated condition, add the instrument and accessory burdens, and compare the result with the selected CT's documented burden/accuracy envelope. The worksheet intentionally has no illustrative numbers: an example using convenient figures could be mistaken for an orderable RITOKS DP or BH configuration.
When the Run Is Too Long
If the completed assessment does not meet the selected CT's requirements, the response is a design change, not an undocumented claim of “acceptable tolerance.” Potential changes include a larger secondary conductor, a different cable route, a meter closer to the CT, or a compatible CT/receiver combination with a documented lower-current secondary. Schneider Electric lists these as general burden-reduction approaches. Their feasibility depends on the exact products and cabinet design.
Another route is to use a finished transducer nearer the sensing point and transmit its specified process signal over the long run. That changes the architecture: it can require auxiliary power, a different receiver and separate insulation and accuracy review. The RITOKS AC Current Transducers category is an adjacent family, not proof that any particular transducer replaces the selected CT. Keep the architecture change visible in the scope and quotation.
Do not shorten the documented run only on paper or omit a test switch to make a total pass. Likewise, do not transfer another manufacturer's burden rating to a RITOKS model with a similar ratio. A defensible selection is one supported by the exact CT, meter, cable and installation evidence.
Secondary Safety and Commissioning
The secondary circuit of a conventional CT must be installed and maintained under its manufacturer's safety instructions. Improperly opening a CT secondary while primary current is present can create a hazard. This article does not provide a wiring, shorting or live-work procedure. The panel designer should specify the appropriate test/shorting arrangement, qualified installation method and commissioning checks for the actual equipment.
After installation, record the CT identity, ratio, secondary, lead route, cable size, measured burden or calculated evidence, meter input and scaling. Verify the reading and direction under an approved method. If the cable route changes during construction, rerun the burden assessment rather than treating the earlier worksheet as permanent. A later meter replacement likewise requires review of its input burden.
RFQ Questions That Resolve the Calculation
Send RITOKS and the instrument supplier the following joined request:
- Identify the exact CT family, frame, ratio, secondary current and required accuracy condition.
- Request the exact-model rated burden, frequency, insulation and installation documents.
- Identify the meter, its input specification and rated burden at the intended secondary current.
- Supply the two-way cable route, conductor material and area, terminal or test-block details and installation environment.
- State whether any alternative CT secondary or signal architecture is acceptable to the design authority.
- Include quantity, destination and documentation requirements, and ask for the full orderable designation.
Start at the RITOKS Current Transformers category or the specific BH-0.66 60I e DP split-core pages, then contact RITOKS with the completed inputs. Burden is a property of the selected CT plus its connected circuit. The correct answer emerges from that complete chain, not from cable length alone.
Source notes
- RITOKS Current Transformers, BH-0.66 60I e DP split-core: distinct product-family facts and missing DP data.
- Schneider Electric CT burden FAQ e wire-length FAQ: primary manufacturer guidance on adding lead and instrument burden.
- Phoenix Contact current transformers: 1 A and 5 A examples in that manufacturer's range only.
- Schneider Electric PM5100 specifications: illustration that a receiver has exact input and burden fields; no ratings transferred.