{"id":2247,"date":"2026-10-06T06:14:53","date_gmt":"2026-10-06T06:14:53","guid":{"rendered":"http:\/\/ritoks.com\/"},"modified":"2026-10-06T06:14:53","modified_gmt":"2026-10-06T06:14:53","slug":"current-transformer-ratio-selection","status":"publish","type":"post","link":"https:\/\/ritoks.com\/pl\/current-transformer-ratio-selection\/","title":{"rendered":"Current Transformer Ratio Selection: Primary Current and Secondary Output"},"content":{"rendered":"<p class=\"wp-block-paragraph\">Specify a current transformer ratio from the primary circuit, secondary measurement input and exact burden and accuracy evidence. A useful buyer review connects the project requirement to one exact orderable product and preserves the evidence used for approval.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">This guide explains the evidence chain for a current-transformer ratio. It does not calculate a project ratio, declare compatibility with a meter or protection relay, or provide secondary wiring or safety instructions.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Podsumowanie danych wej\u015bciowych do decyzji<\/h2>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Pole recenzji<\/th><th>Kupuj\u0105cy musi okre\u015bli\u0107<\/th><th>Dokumenty, o kt\u00f3rych udost\u0119pnienie nale\u017cy wyst\u0105pi\u0107<\/th><\/tr><\/thead><tbody><tr><td>Primary current<\/td><td>Normal, maximum and relevant operating range<\/td><td>Project load study<\/td><\/tr><tr><td>Wyj\u015bcie wt\u00f3rne<\/td><td>Exact input required by the receiving meter or relay<\/td><td>Receiving-device manual<\/td><\/tr><tr><td>Wsp\u00f3\u0142czynnik<\/td><td>Declared primary-to-secondary relationship<\/td><td>Exact CT model row<\/td><\/tr><tr><td>Measurement performance<\/td><td>Accuracy and burden under documented conditions<\/td><td>Manufacturer data and system calculation<\/td><\/tr><tr><td>Pasowanie mechaniczne<\/td><td>Window, conductor, mounting and installation constraints<\/td><td>Drawing and installation review<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<figure data-spectra-id=\"spectra-d54d1b7c-09d3-4c6a-84ec-e3139e32b9b2\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01.webp\" alt=\"Current transformer ratio selection input map for primary current and secondary measurement interface\" class=\"wp-image-2245\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-01-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">The ratio must connect the real primary circuit to the exact receiving-device input.<\/figcaption><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Start With the Real Primary Current Range<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The primary side should be described by the expected operating current, maximum normal condition and any meaningful variation that affects measurement. Selecting from conductor ampacity or protective-device frame size alone can place normal readings in an unsuitable part of the measurement range.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Record how the current estimate was obtained and whether future operating modes change it. The buyer does not need to force a final ratio before the receiving-device input and measurement objective are known.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Match the Secondary Output to the Receiving Device<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A current transformer and a meter form an interface. The CT secondary declaration must match the exact input expected by the meter, transducer or relay. A familiar ratio notation is not enough to establish that relationship. Request both documents and review them together.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Do not use a product family page to infer input compatibility. Neighboring meter variants may accept different sensors or secondary signals. The approval record must name the exact receiving device and its terminal documentation.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Understand What the Ratio Expresses<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The ratio states the declared relationship between primary current and secondary output under the product&#8217;s defined conditions. It does not by itself establish accuracy across the required operating range, available burden, saturation behavior or suitability for protection. Those are separate evidence fields.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">When quotations offer different ratios, compare the resulting measurement use rather than treating the values as catalog alternatives. Each proposal should explain how the ratio aligns with the project&#8217;s primary-current range and receiving input.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Review Burden and Accuracy as a System<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The connected input, lead path and terminals contribute to the secondary circuit seen by the transformer. The responsible engineer should calculate and verify that complete circuit against the exact CT and receiving-device documents. Procurement should preserve the inputs rather than guessing from a headline accuracy class.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Ask where accuracy is declared, at which conditions and for which order code. Never combine the ratio of one model, burden data from another and dimensions from a third. If the system calculation is missing, mark the proposal incomplete.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Confirm Frequency, Purpose and Operating Context<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">State whether the measurement supports indication, energy monitoring, control, protection or another purpose. These uses can demand different evidence. Also record the system frequency and waveform context that the manufacturer requires for its declaration.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">This guide deliberately avoids treating a measurement CT as a protection CT or vice versa. The proposed device must be documented for the intended role, and any special behavior must be evaluated by the system designer.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Verify Window Size and Installation Constraints<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The primary conductor, bar arrangement, insulation, bending space and access determine whether the CT can be installed. A ratio match does not prove mechanical fit. Request the exact outline drawing and confirm that the window accommodates the real conductor without unsupported modification.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">For retrofit work, a split-core construction may change installation access, but it does not remove the need to review ratio, output, burden, accuracy and environmental conditions. Keep construction choice separate from electrical approval.<\/p>\n\n\n\n<figure data-spectra-id=\"spectra-7c16048c-c945-410b-8d19-e1b1e4688e3b\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02.webp\" alt=\"Current transformer exact-model verification stack for ratio, burden, accuracy and window fit\" class=\"wp-image-2246\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-body-02-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">Ratio is only one field in a complete CT approval record.<\/figcaption><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Stw\u00f3rz plik dowod\u00f3w oparty na modelu dok\u0142adnym<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Create one approval record for the proposed Current Transformer order code. Put each project requirement beside the supplier document that answers it. Preserve the exact datasheet, drawing, table, instruction or selection output used, including its revision or retrieval date. A category page can establish family context, but it cannot prove an exact rating, terminal arrangement or system combination.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Nale\u017cy sprawdzi\u0107, czy ka\u017cda zaakceptowana specyfikacja dotyczy tej samej pozycji dost\u0119pnej w ofercie. Podobne obudowy mog\u0105 zawiera\u0107 r\u00f3\u017cne uk\u0142ady elektroniczne, zasilacze, zaciski, akcesoria lub funkcje. Nie nale\u017cy \u0142\u0105czy\u0107 maksymalnej liczby sztuk z jednej rodziny z wariantem, schematem z innego wariantu oraz opcjonaln\u0105 funkcj\u0105 z trzeciego. Nale\u017cy wyra\u017anie oznaczy\u0107 pola, kt\u00f3re nie zosta\u0142y jeszcze wype\u0142nione, tak aby pozosta\u0142y widoczne podczas przegl\u0105du handlowego.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Nale\u017cy oddziela\u0107 dane wej\u015bciowe projektu od dowod\u00f3w dotycz\u0105cych produktu<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The project team defines the application: source, load, duty, environment, controls, mechanical limits and required functions. The supplier identifies an exact Current Transformer and supports it with exact documents. Neither side should fill a gap by inference from appearance, a shared family name or one matching headline value.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Nale\u017cy wstrzyma\u0107 proces rozpatrywania wniosku na czas por\u00f3wnywania ofert. Je\u015bli zmieni\u0105 si\u0119 topologia, \u017ar\u00f3d\u0142o, obci\u0105\u017cenie, \u015brodowisko, obudowa lub wymagana moc wyj\u015bciowa, nale\u017cy sporz\u0105dzi\u0107 zaktualizowany dokument i poprosi\u0107 ka\u017cdego dostawc\u0119 o ponowne potwierdzenie wybranego rozwi\u0105zania. W przeciwnym razie oferty, kt\u00f3re na pierwszy rzut oka wydaj\u0105 si\u0119 por\u00f3wnywalne, mog\u0105 odpowiada\u0107 na r\u00f3\u017cne wymagania techniczne.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Typowe b\u0142\u0119dy zwi\u0105zane z zam\u00f3wieniami publicznymi<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Avoid selecting a Current Transformer from one headline value while the application context remains incomplete. Do not use a circuit, curve, terminal drawing or performance claim from a neighboring model. A product photograph and a family page can support discovery, but neither is exact technical evidence.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Nale\u017cy r\u00f3wnie\u017c unika\u0107 zak\u0142adania, \u017ce dany element wyposa\u017cenia, funkcja komunikacyjna, rola ochronna lub skoordynowany wynik s\u0105 uwzgl\u0119dnione, o ile nie zosta\u0142y one wymienione w ofercie cenowej i dokumentacji dotycz\u0105cej konkretnego modelu. Produkt zast\u0119pczy musi spe\u0142nia\u0107 te same wymagania dotycz\u0105ce topologii, parametr\u00f3w znamionowych, sposobu monta\u017cu oraz weryfikacji dokumentacji, co pierwotnie rozwa\u017cany produkt.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Jak por\u00f3wna\u0107 oferty dostawc\u00f3w<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Normalize every Current Transformer offer to the same application record. Keep document revisions, stated conditions, included accessories and open questions beside each value. This makes differences in delivered scope visible and prevents a lower-cost but narrower offer from appearing equivalent to a complete solution.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Nale\u017cy zaprzesta\u0107 por\u00f3wnywania, gdy nieznane s\u0105 kluczowe parametry aplikacji, podany model jest niejednoznaczny, wymagana specyfikacja jest poparta jedynie danymi innego producenta lub kodem zam\u00f3wienia, albo gdy instalacja wykracza poza zakres dost\u0119pnych danych. S\u0105 to luki techniczne, a nie szczeg\u00f3\u0142y redakcyjne.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Kontrola zmian i zamian<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Give the approved Current Transformer record a revision identifier and keep it with the project file. If the supplier changes the order code, accessory, firmware, drawing or stated operating condition, identify the change before accepting it. A substitution is a new technical proposal even when its price, housing or product-family name looks familiar.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Powt\u00f3rz tylko te kontrole, kt\u00f3rych dotyczy problem, ale nie rezygnuj z nich. Upewnij si\u0119, \u017ce zaktualizowana wersja wniosku nadal odpowiada zamro\u017conemu wnioskowi, \u017ce wszystkie dokumenty, do kt\u00f3rych si\u0119 odwo\u0142uje, nale\u017c\u0105 do niego oraz \u017ce wszystkie otwarte wyj\u0105tki maj\u0105 wyznaczonego odpowiedzialnego. Ten niewielki etap kontroli zmian zapobiega zast\u0105pieniu selekcji, kt\u00f3ra przesz\u0142a weryfikacj\u0119 techniczn\u0105, przez jej niepoddan\u0105 weryfikacji komercyjn\u0105 wersj\u0119.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Proces podejmowania decyzji<\/h2>\n\n\n\n<ul class=\"wp-block-list\"><li>Przed wybraniem kodu katalogowego nale\u017cy zablokowa\u0107 aplikacj\u0119 i zapis systemowy.<\/li><li>Nale\u017cy okre\u015bli\u0107 dok\u0142adn\u0105 funkcj\u0119 oraz ka\u017cdy interfejs, kt\u00f3ry wymaga potwierdzenia.<\/li><li>Prosz\u0119 o przes\u0142anie jednego kompletnego kodu zam\u00f3wienia wraz z aktualn\u0105 kart\u0105 katalogow\u0105 i rysunkami technicznymi.<\/li><li>Nale\u017cy przyporz\u0105dkowa\u0107 ka\u017cde wymaganie projektowe do konkretnego o\u015bwiadczenia producenta.<\/li><li>Nale\u017cy odnotowa\u0107 odchylenia, elementy dodatkowe, zmiany w dokumentacji oraz nierozstrzygni\u0119te kwestie.<\/li><li>Nale\u017cy powt\u00f3rzy\u0107 przegl\u0105d za ka\u017cdym razem, gdy nast\u0105pi\u0105 zmiany w zastosowaniu lub w proponowanym produkcie.<\/li><\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">Use this workflow as a procurement and evidence discipline. It does not replace qualified design, installation instructions or the responsible engineer&#8217;s approval for the Current Transformer application.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Lista kontrolna dotycz\u0105ca przygotowania zapytania ofertowego<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A practical current transformer ratio selection should be concise enough for a supplier to answer and complete enough to prevent silent assumptions. Identify unknown values as questions rather than allowing them to become undocumented selections.<\/p>\n\n\n\n<ul class=\"wp-block-list\"><li>Primary current: Normal, maximum and relevant operating range.<\/li><li>Secondary output: Exact input required by the receiving meter or relay.<\/li><li>Ratio: Declared primary-to-secondary relationship.<\/li><li>Measurement performance: Accuracy and burden under documented conditions.<\/li><li>Mechanical fit: Window, conductor, mounting and installation constraints.<\/li><li>Dok\u0142adny kod produktu, zawarte w zestawie akcesoria oraz wersja dokumentacji<\/li><li>Ilo\u015b\u0107, miejsce przeznaczenia, wymagane zezwolenia oraz zakres handlowy<\/li><\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">Nale\u017cy poprosi\u0107 o dok\u0142adny zakres wszelkich o\u015bwiadcze\u0144 dotycz\u0105cych klasyfikacji, zgodno\u015bci, koordynacji lub wydajno\u015bci. Nale\u017cy odnotowa\u0107 ilo\u015b\u0107 i miejsce przeznaczenia po danych technicznych, aby warunki handlowe nie przes\u0142ania\u0142y nierozstrzygni\u0119tych kwestii technicznych.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Najcz\u0119\u015bciej zadawane pytania<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">Can CT ratio be selected from breaker size alone?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">No. Use the real current range, receiving-device input and measurement objective.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Does a matching secondary value prove compatibility?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">No. Burden, accuracy, frequency, terminals and the exact interface still require review.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Can a current transformer secondary be treated as an ordinary signal?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">No. Follow qualified design practices and the exact manufacturer safety instructions.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Powi\u0105zane produkty i wytyczne firmy RITOKS<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Linki te s\u0142u\u017c\u0105 wy\u0142\u0105cznie do przedstawienia kontekstu rodziny produkt\u00f3w. Link kontekstowy nie oznacza zamienno\u015bci, kompatybilno\u015bci ani zatwierdzonej kombinacji system\u00f3w.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/pl\/product-category\/electrical-measurement-monitoring\/current-transformers\/\">Current Transformer product category<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/pl\/products\/bh-0-66-60i-current-transformer-200-5a-1500-5a\/\">BH-0.66-60I current transformer family<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/pl\/products\/dp-series-split-core-current-transformer\/\">Przek\u0142adnik pr\u0105dowy z dzielonym rdzeniem serii DP<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/pl\/products\/gta20l-precision-current-transformer-10a-100a\/\">GTA20L precision current transformer<\/a><\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Materia\u0142y techniczne<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Powy\u017csze \u017ar\u00f3d\u0142a producenta s\u0142u\u017c\u0105 wy\u0142\u0105cznie do zilustrowania og\u00f3lnych zasad technicznych opisanych poni\u017cej. Dane techniczne produkt\u00f3w, schematy obwod\u00f3w, certyfikaty oraz wyniki koordynacji z tych \u017ar\u00f3de\u0142 nie maj\u0105 zastosowania do produkt\u00f3w RITOKS.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/www.se.com\/us\/en\/product-subcategory\/4115-powerlogic-multifunction-power-meters\/\" target=\"_blank\" rel=\"noopener\">Schneider Electric, wielofunkcyjne mierniki mocy PowerLogic<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Supports treating the meter input and measurement architecture as part of the complete system record. Schneider meter inputs do not establish compatibility with RITOKS CTs.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Popro\u015b o przegl\u0105d konkretnego modelu<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Prosimy o przes\u0142anie wymaga\u0144 dotycz\u0105cych zam\u00f3wienia, szczeg\u00f3\u0142owych pyta\u0144 dotycz\u0105cych dokumentacji, ilo\u015bci i miejsca dostawy za po\u015brednictwem formularza kontaktowego RITOKS. Zapytanie ofertowe wymaga weryfikacji konkretnego modelu; niniejszy przewodnik nie zatwierdza obwod\u00f3w, instalacji ani automatycznych zamiennik\u00f3w.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/pl\/contact-us\/\">Skontaktuj si\u0119 z firm\u0105 RITOKS<\/a><\/p>","protected":false},"excerpt":{"rendered":"<p>Specify a current transformer ratio from the primary circuit, secondary measurement input and exact burden and accuracy evidence.<\/p>","protected":false},"author":1,"featured_media":2244,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":"viox","ritoks_resource_product_cat_term_id":26,"footnotes":""},"categories":[68],"tags":[],"class_list":["post-2247","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-electrical-measurement-monitoring"],"acf":[],"spectra_blocks_featured_image_url":{"thumbnail":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-hero-01-150x150.webp","width":150,"height":150},"medium":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-hero-01-300x169.webp","width":300,"height":169},"medium_large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-hero-01-768x432.webp","width":768,"height":432},"large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-hero-01-1024x576.webp","width":1024,"height":576},"full":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/current-transformer-ratio-selection-hero-01.webp","width":1600,"height":900}},"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/pl\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/posts\/2247","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/comments?post=2247"}],"version-history":[{"count":1,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/posts\/2247\/revisions"}],"predecessor-version":[{"id":2248,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/posts\/2247\/revisions\/2248"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/media\/2244"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/media?parent=2247"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/categories?post=2247"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/pl\/wp-json\/wp\/v2\/tags?post=2247"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}