{"id":3958,"date":"2026-11-10T06:28:06","date_gmt":"2026-11-10T06:28:06","guid":{"rendered":"http:\/\/ritoks.com\/"},"modified":"2026-11-10T06:28:06","modified_gmt":"2026-11-10T06:28:06","slug":"4-20ma-vs-0-10v-current-transducer-outputs","status":"publish","type":"post","link":"https:\/\/ritoks.com\/pt-br\/4-20ma-vs-0-10v-current-transducer-outputs\/","title":{"rendered":"4\u201320 mA vs 0\u201310 V Current Transducer Outputs"},"content":{"rendered":"<p class=\"wp-block-paragraph\">An industrial current transducer has two different electrical questions: what current does it measure, and what signal does it send to the monitoring system? A 4\u201320 mA or 0\u201310 V label usually describes the second question. Neither output range tells a buyer whether the measured conductor carries AC or DC, whether the transducer is isolated, how it is powered, or whether the controller can accept its signal. The right comparison therefore starts at the receiving input and traces backward through the complete measurement chain.<\/p>\n<p class=\"wp-block-paragraph\">O <a href=\"https:\/\/ritoks.com\/pt-br\/product-category\/electrical-measurement-monitoring\/dc-current-transducers\/\">RITOKS DC Current Transducers category<\/a> includes a published <a href=\"https:\/\/ritoks.com\/pt-br\/products\/wbi334u01-s-dc-current-transducer-4-20ma\/\">WBI334U01-S DC current transducer<\/a> with documented 0\u201320 mA or 4\u201320 mA output choices. The available public evidence does <strong>not<\/strong> establish a RITOKS current-transducer model with a 0\u201310 V output. This article compares two common interface architectures so a buyer can write a better specification; it does not claim that both are offered on that RITOKS product or that its current output can be reconfigured to voltage output.<\/p>\n<figure class=\"wp-block-table\"><table>\n<thead>\n<tr>\n<th>Campo de solicita\u00e7\u00e3o de cota\u00e7\u00e3o<\/th>\n<th>4\u201320 mA route<\/th>\n<th>0\u201310 V route<\/th>\n<\/tr>\n<\/thead>\n<tbody><tr>\n<td>Receiver<\/td>\n<td>Compatible current input<\/td>\n<td>Compatible voltage input<\/td>\n<\/tr>\n<tr>\n<td>Nominal low endpoint<\/td>\n<td>4 mA, if the exact model uses that range<\/td>\n<td>0 V, if the exact model uses that range<\/td>\n<\/tr>\n<tr>\n<td>Fornecimento<\/td>\n<td>Check active\/passive loop and exact supply<\/td>\n<td>Check transmitter supply and output drive<\/td>\n<\/tr>\n<tr>\n<td>Wiring<\/td>\n<td>Verify loop load and return<\/td>\n<td>Verify input impedance, reference and cable conditions<\/td>\n<\/tr>\n<tr>\n<td>Available RITOKS evidence<\/td>\n<td>WBI334U01-S documents 4\u201320 mA option<\/td>\n<td>No current-transducer 0\u201310 V offer verified here<\/td>\n<\/tr>\n<\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">These are interface questions, not a universal wiring diagram. The selected manufacturer&#8217;s datasheet and receiver manual govern the actual connection.<\/p>\n<h2 class=\"wp-block-heading\">Separate Measured Current From Output Signal<\/h2>\n<p class=\"wp-block-paragraph\">The measured input may be a small DC current on dedicated terminals, an AC conductor through an aperture, or another arrangement entirely. The output may then be an analog current, analog voltage or digital protocol. Input and output ranges should have distinct lines in the equipment schedule. If a purchase request says only \u201c4\u201320 mA current sensor,\u201d it leaves the measured current range, current direction, sensing arrangement and auxiliary supply unresolved.<\/p>\n<p class=\"wp-block-paragraph\">The published WBI334U01-S page describes a zero-to-positive DC input architecture with supplier-defined nominal input options and a 0\u201320 mA or 4\u201320 mA DC output choice. It is not documented as a bidirectional high-current busbar sensor. A different RITOKS family, the <a href=\"https:\/\/ritoks.com\/pt-br\/products\/hs2v-h02-open-loop-hall-current-sensors\/\">HS2V H02 Hall sensor<\/a>, has an analog voltage output at nominal primary current, but that published output is \u00b14 V, not 0\u201310 V. Neither product should be relabeled to fit an input-module specification.<\/p>\n<p class=\"wp-block-paragraph\">Before comparing output formats, write down waveform, nominal measured current, expected minimum and maximum, whether current reverses, and the physical conductor or terminal geometry. Then identify a candidate transducer whose published input architecture matches. Only after that should the engineer choose an output format and receiving channel. This order prevents a familiar PLC signal type from driving an inappropriate sensing choice.<\/p>\n<h2 class=\"wp-block-heading\">How the Receiving Input Changes the Decision<\/h2>\n<p class=\"wp-block-paragraph\">A controller with a current-input channel needs the transducer&#8217;s specified current range, input burden and wiring configuration to match. A 4\u201320 mA output does not become a 0\u201310 V output merely because both represent a process variable. <a href=\"https:\/\/www.phoenixcontact.com\/en-ch\/technologies\/industrial-signal-processing\/digital-and-analog-signal-conditioning\" target=\"_blank\" rel=\"noopener\">Phoenix Contact&#8217;s signal-conditioning guidance<\/a> explicitly gives a 4\u201320 mA transmitter feeding a 0\u201310 V evaluation unit as an example requiring a separate standard-signal converter. That converter is an additional specified component, not an assumed feature of the transducer.<\/p>\n<p class=\"wp-block-paragraph\">For a voltage-input route, obtain the receiver&#8217;s accepted range, input impedance, reference arrangement and any differential or isolated-input capability. A module labeled \u201canalog input\u201d may have configurable channels, but the installed terminal configuration and software range still need confirmation. When input channels are shared across multiple signal types, a procurement drawing should name the exact channel and configuration, not only the controller model.<\/p>\n<figure data-spectra-id=\"spectra-f8faa7fe-e8ed-4c83-8aaa-2af66e623c4f\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01.webp\" alt=\"Separate generic current and voltage outputs matched to corresponding receiver input types\" class=\"wp-image-3956\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-01-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">A format mismatch requires a documented conditioner or another exact model.<\/figcaption><\/figure>\n<p class=\"wp-block-paragraph\">Also ask what a missing or invalid signal should mean to the control system. A 4 mA live-zero convention can provide room below the normal measured range for fault discrimination in a correctly designed system; it is not automatic cable-break detection for every transmitter and every PLC. A 0 V low endpoint may represent valid zero or a disconnected circuit depending on the output and receiver design. Alarm limits, out-of-range interpretation and fault diagnostics are system functions that must be configured and tested.<\/p>\n<h2 class=\"wp-block-heading\">Cable, Load and Noise Are System Properties<\/h2>\n<p class=\"wp-block-paragraph\">Analog current loops are often selected when signal transmission over a longer cable or in electrically noisy areas matters. <a href=\"https:\/\/www.analog.com\/en\/resources\/design-notes\/selectablerange-current-loop.html\" target=\"_blank\" rel=\"noopener\">Analog Devices&#8217; current-loop design note<\/a> explains that loop current is comparatively insensitive to line resistance within the designed operating limits. <a href=\"https:\/\/blog.phoenixcontact.com\/marketing-gb\/wp-content\/uploads\/sites\/3\/2018\/09\/52007057_EN_MCR_technology_User_manual.pdf\" target=\"_blank\" rel=\"noopener\">Phoenix Contact&#8217;s analog-signal manual<\/a> similarly contrasts current and voltage transmission under cable and interference conditions. These sources describe engineering tendencies, not a guaranteed cable length for any RITOKS model.<\/p>\n<p class=\"wp-block-paragraph\">A current-loop advantage disappears if the supply cannot drive the transmitter plus receiver burden and cable resistance. Ask for the exact permissible load and compliance range of the selected output. Check the real controller input and cable route rather than repeating a generic \u201clong distance\u201d promise. If a current output is passive, the loop may require an external supply; if active, the power and reference arrangement may be different. The term \u201c4\u201320 mA\u201d alone does not decide active versus passive.<\/p>\n<p class=\"wp-block-paragraph\">A voltage output likewise needs a compatible receiver input and suitable reference. Long leads and ground-potential differences can add error or interference. Differential inputs, isolation, cable construction and routing can matter, but none can be prescribed from an output label alone. <a href=\"https:\/\/www.ni.com\/en\/shop\/data-acquisition\/sensor-fundamentals\/measuring-direct-current-dc-voltage.html\" target=\"_blank\" rel=\"noopener\">National Instruments&#8217; voltage-measurement guide<\/a> identifies ground loops, common-mode voltage and isolation topology as measurement considerations. The cabinet engineer should review the actual installation against those principles.<\/p>\n<h2 class=\"wp-block-heading\">Keep Output, Supply and Isolation in Separate Rows<\/h2>\n<p class=\"wp-block-paragraph\">Three lines in an RFQ are easily confused: measured current, output signal and auxiliary supply. For WBI334U01-S, the public page lists 12 V or 24 V DC auxiliary-supply options and 0\u201320 mA or 4\u201320 mA output options. The supply voltage is not the measurement output. It also describes an electromagnetic-isolation principle, but exact insulation ratings and installation suitability still require the selected manufacturer&#8217;s documentation. Do not reuse these facts for an unverified 0\u201310 V variant.<\/p>\n<p class=\"wp-block-paragraph\">The output interface may be isolated from input, supply or both, with different limits. A marketing word such as \u201cisolated\u201d is incomplete until the relevant barrier, test\/rated voltage, working-voltage context and applicable standard are clear. The controller&#8217;s analog input might itself be isolated or might share a reference with other channels. A transducer and receiving device must be reviewed as one signal chain; either component&#8217;s isolation label does not certify the whole panel.<\/p>\n<p class=\"wp-block-paragraph\">Write the supply specification with voltage, polarity, source, tolerance and available current. For a current loop, add active\/passive status, permissible load and required receiver burden. For voltage output, add the available output drive, receiver impedance and grounding scheme. Keep unknown fields explicitly open. A placeholder \u201cstandard 24 V\u201d on a schedule is not an adequate substitute for exact-model evidence.<\/p>\n<h2 class=\"wp-block-heading\">Scaling and Commissioning Should Be Specified Together<\/h2>\n<p class=\"wp-block-paragraph\">An analog signal has meaning only after the receiver scales it to the actual measured current range. If the nominal transducer input is selected for one current span and the PLC scales 4\u201320 mA to another, the displayed amperes can be wrong while the electrical interface still appears healthy. The order sheet should pair the selected input span with the output span and the controller&#8217;s engineering-unit scaling. Document the zero, span, direction and any expected overload indication.<\/p>\n<p class=\"wp-block-paragraph\">For a 4\u201320 mA device, 4 mA at the low endpoint and 20 mA at the high endpoint are only the ideal mapping if the exact product defines that relationship. Do not assume bidirectional current is represented symmetrically or that every product can be recalibrated in the field. For a proposed 0\u201310 V current transducer, request a verified datasheet showing its measured input, transfer function, offset, load and supply before approving the channel. A general 0\u201310 V controller input does not prove that such a compatible RITOKS current transducer is currently available.<\/p>\n<p class=\"wp-block-paragraph\">Commissioning should include a signal-chain check under a safe, documented procedure: exact order code, terminal assignment, polarity or reference, input-module range, displayed engineering units and known test points. The manufacturer&#8217;s instructions and a qualified commissioning plan determine how those checks are performed. This article intentionally avoids prescribing live electrical test wiring.<\/p>\n<h2 class=\"wp-block-heading\">Build a Procurement Schedule That Can Be Answered<\/h2>\n<p class=\"wp-block-paragraph\">An RFQ should make the supplier&#8217;s confirmation task concrete. Include:<\/p>\n<ol class=\"wp-block-list\">\n<li>Measured current type, direction, nominal range, normal low and high values, and any pulse or transient requirement.<\/li>\n<li>Physical sensing arrangement, conductor or terminal details, available panel space, mounting and environment.<\/li>\n<li>Required output format, receiver model, actual input-channel range and engineering-unit scaling.<\/li>\n<li>Auxiliary supply and active\/passive loop arrangement, if a current-output route is proposed.<\/li>\n<li>Cable route, receiver burden or impedance, grounding and isolation requirements to be confirmed.<\/li>\n<li>Exact model datasheet, terminal drawing, applicable documentation, quantity and destination market.<\/li>\n<\/ol>\n<figure data-spectra-id=\"spectra-2f2feb2b-804c-45cf-8f51-fe90fea3cb30\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02.webp\" alt=\"Blank current-transducer RFQ fields for input, output, receiver and supply or isolation\" class=\"wp-image-3957\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-body-02-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">Supply and receiver fields are separate from measured current.<\/figcaption><\/figure>\n<p class=\"wp-block-paragraph\">If the controller only accepts voltage while the available verified current transducer provides a current loop, request an engineered signal conditioner and its wiring evidence, or ask the supplier for a separately documented voltage-output model. Do not silently substitute the <a href=\"https:\/\/ritoks.com\/pt-br\/products\/vdt-20-din-rail-ac-voltage-transducer\/\">VDT-20 voltage transducer<\/a> because it offers 0\u201310 V: VDT-20 measures <strong>Tens\u00e3o CA<\/strong>, not current. Distinguishing these product families is essential to a useful quote.<\/p>\n<h2 class=\"wp-block-heading\">Selection Summary<\/h2>\n<p class=\"wp-block-paragraph\">Choose 4\u201320 mA when the exact current transducer, loop supply, receiver and cable design support that interface and the system&#8217;s scaling and diagnostics are defined. Choose a 0\u201310 V route only when an exact current-transducer model with that output is documented and the receiving input, grounding and cable conditions fit. Neither signal is inherently better without the installation context.<\/p>\n<p class=\"wp-block-paragraph\">For RITOKS, the documented starting point is the <a href=\"https:\/\/ritoks.com\/pt-br\/products\/wbi334u01-s-dc-current-transducer-4-20ma\/\">WBI334U01-S current-output family<\/a> within <a href=\"https:\/\/ritoks.com\/pt-br\/product-category\/electrical-measurement-monitoring\/dc-current-transducers\/\">Transdutores de corrente cont\u00ednua<\/a>. State a voltage-output requirement openly in the <a href=\"https:\/\/ritoks.com\/pt-br\/contact-us\/\">RITOKS inquiry<\/a> instead of treating an undocumented version as orderable. A buyer who separates measured current, output signal, supply, receiver and isolation will receive a more testable technical response.<\/p>\n<h2 class=\"wp-block-heading\">Source notes<\/h2>\n<ul class=\"wp-block-list\">\n<li><a href=\"https:\/\/ritoks.com\/pt-br\/products\/wbi334u01-s-dc-current-transducer-4-20ma\/\">RITOKS WBI334U01-S DC current transducer<\/a>: model-specific input architecture, output and supply choices.<\/li>\n<li><a href=\"https:\/\/ritoks.com\/pt-br\/product-category\/electrical-measurement-monitoring\/dc-current-transducers\/\">RITOKS DC Current Transducers category<\/a>: family ownership and non-equivalence to other current sensors.<\/li>\n<li><a href=\"https:\/\/www.phoenixcontact.com\/en-ch\/technologies\/industrial-signal-processing\/digital-and-analog-signal-conditioning\" target=\"_blank\" rel=\"noopener\">Phoenix Contact signal conditioning<\/a> e <a href=\"https:\/\/blog.phoenixcontact.com\/marketing-gb\/wp-content\/uploads\/sites\/3\/2018\/09\/52007057_EN_MCR_technology_User_manual.pdf\" target=\"_blank\" rel=\"noopener\">analog-signal transmission manual<\/a>: interface conversion, load and cable considerations.<\/li>\n<li><a href=\"https:\/\/www.analog.com\/en\/resources\/design-notes\/selectablerange-current-loop.html\" target=\"_blank\" rel=\"noopener\">Analog Devices current-loop note<\/a>: current-loop transmission context.<\/li>\n<li><a href=\"https:\/\/www.ni.com\/en\/shop\/data-acquisition\/sensor-fundamentals\/measuring-direct-current-dc-voltage.html\" target=\"_blank\" rel=\"noopener\">National Instruments voltage measurement<\/a>: reference, ground-loop and isolation considerations.<\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>Compare current-loop and voltage-output interfaces by receiver, supply, cable and scaling without assuming an undocumented 0\u201310 V RITOKS current-transducer model.<\/p>","protected":false},"author":1,"featured_media":3955,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":"viox","ritoks_resource_product_cat_term_id":123,"footnotes":""},"categories":[68],"tags":[],"class_list":["post-3958","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-electrical-measurement-monitoring"],"acf":[],"spectra_blocks_featured_image_url":{"thumbnail":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-hero-01-150x150.webp","width":150,"height":150},"medium":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-hero-01-300x169.webp","width":300,"height":169},"medium_large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-hero-01-768x432.webp","width":768,"height":432},"large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-hero-01-1024x576.webp","width":1024,"height":576},"full":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/11\/4-20ma-vs-0-10v-current-transducer-outputs-hero-01.webp","width":1600,"height":900}},"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/pt-br\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/posts\/3958","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/comments?post=3958"}],"version-history":[{"count":1,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/posts\/3958\/revisions"}],"predecessor-version":[{"id":3959,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/posts\/3958\/revisions\/3959"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/media\/3955"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/media?parent=3958"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/categories?post=3958"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/pt-br\/wp-json\/wp\/v2\/tags?post=3958"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}