Filter Fan Airflow vs Free-Air Fan Rating
A free-air fan rating and the air actually moving through a filtered electrical enclosure are different quantities. The fan may be tested or quoted with little external restriction; the installed path adds the filter mat, grille, cabinet openings, internal components and an exhaust route. The operating airflow depends on the fan's pressure-flow behavior and the resistance of that complete path. Selecting a cabinet filter fan from motor watts, RPM or a bare fan's maximum airflow can therefore leave the enclosure short of its cooling requirement.

RITOKS publishes an FD Series cabinet filter-fan family och en Cabinet Cooling Fans category. The FD page lists nine fan-kit configurations with model-specific supply, motor power and speed, plus four grille references. It does not publish complete airflow or static-pressure curves for those configurations. The FD9802.300 grille's listed dimensions and IP54 data are specific to that reference, not a family-wide performance claim. This guide defines the evidence to request instead of manufacturing a CFM comparison from RPM.
Three Airflow Numbers That Can Be Confused
The phrase “free-air airflow” generally describes a fan or assembly under very low external pressure. It can be useful for comparing test conditions, but it does not guarantee the flow when a filter and cabinet are attached. A filter-fan assembly may also have a catalog airflow with a specified filter or exhaust configuration. Finally, installed system airflow is what passes through the actual enclosure under its real pressure losses. These quantities must be labeled with their test conditions to compare them honestly.
Pfannenberg's filter-fan technical discussion explains that a fan's nominal value can differ substantially from the flow of a filter-fan and exhaust-filter combination because the media and housing resist airflow. Oriental Motor's fan reference shows that filters and other optional parts shift the air-flow/static-pressure behavior. These are primary manufacturer explanations of the principle, not test values for RITOKS FD.
When a supplier quotes an airflow number, ask: which fan model, which grille, which filter media, which exhaust filter, what pressure condition, what supply and what test setup? Without those fields, a number may be a bare-fan maximum or a filtered-assembly point. It should not be used as the delivered enclosure flow.
Why a Filter Changes the Operating Point
Air must cross the intake assembly, move through the cabinet and leave through an outlet. Each element resists flow. The fan has a characteristic relationship between airflow and static pressure; the system has its own resistance relationship. Their intersection is the operating point. Changing the filter, outlet size or internal layout can move that point. This is why “more RPM” alone cannot establish how much cooling air reaches the hot components.
As dust accumulates in a filter, the resistance can increase. A design that only meets a target with a pristine element may have inadequate margin under its maintenance condition. Define the allowed filter service state and replacement practice for the project. Do not claim a universal replacement interval; it depends on dust exposure, media and the manufacturer. If the enclosure has an ingress-protection requirement, choose the exact fan/grille/filter assembly evidence rather than removing media to chase a higher flow number.

Pfannenberg emphasizes that the combination of filter fan and exhaust filter should be considered for a meaningful airflow or cooling assessment. Its own published figures cannot be pasted into the FD range. Ask RITOKS for the matched FD kit, grille and outlet data, including a pressure-flow curve or tested assembly airflow where available. If that evidence is absent, leave the airflow requirement unresolved rather than converting speed into flow.
Heat Load Is a Separate Requirement
Define the heat generated by the cabinet components and the maximum acceptable internal temperature under the site's ambient conditions. A filter fan can exchange cabinet air with ambient air, so it cannot be assumed to cool below the intake-air temperature. The amount of airflow needed depends on the heat balance and allowable temperature rise, as well as airflow path through the heat-producing components. The enclosure designer should perform the calculation using verified heat loads and appropriate assumptions.
Do not equate a fan's electrical motor power with cooling capacity. The FD page's watts are motor power by kit, not measured heat-removal watts for an installed cabinet. Likewise, RPM is rotational speed, not m³/h or CFM. A larger frame may provide an option for more flow, but only exact performance data at the required restriction can support a capacity decision. A supplier can help select the family when the customer provides heat load, ambient and enclosure details.
If outside air is too hot, contaminated or humid for the process, another thermal architecture may be needed. The RITOKS Enclosure Air Conditioners category addresses a separate closed-loop cooling route, not an automatically interchangeable fan upgrade. Keep enclosure heaters, fan ventilation and air conditioners distinct in the scope. A filter fan may solve ventilation where ambient-air exchange is acceptable; it is not a dehumidifier or refrigeration unit.
Check the Complete Intake and Exhaust Path
A useful field sketch shows the air entry, filter fan, intended internal path, outlet or exhaust filter and major obstructions. Ask whether airflow can bypass hot devices, recirculate immediately to the outlet, or be blocked by wiring ducts and packed cable bundles. These are layout questions; no generic arrow graphic can certify real cooling. The installed opening and cutout must match the selected FD kit and grille, with enough panel space for mounting and service.
The FD page lists FD9802.300, FD9803.300, FD9804.300 and FD9805.300 grille options, but only FD9802.300 currently has a complete published dimensional/IP note. Do not extrapolate its 92 × 92 mm cutout or IP54 statement to the other references. Request the exact grille and fan-kit pairing and drawings. A matching series number is a starting point, not proof that all components have identical mounting or environmental ratings.
The outlet deserves as much attention as the intake. An undersized or heavily restricted exhaust can dominate the system loss. Ask for an appropriate exhaust grille/filter and its operating evidence. The direction of fan flow, mounting orientation and protection against ingress must be confirmed from the exact assembly instructions, not guessed from an image. If a panel has other ventilation openings, include them in the system-level assessment rather than assuming a single ideal path.
Compare FD Kits Only on Published Facts
The FD family includes 12 V, 24 V and 230 V variants, with motor power and speed shown by exact kit. These fields help screen the available supply and product reference. They do not establish a ranking of delivered airflow. For example, a 230 V fan-kit row and a 24 V row cannot be compared for cooling solely by watts or RPM because blade design, filter restriction, operating point and test conditions are not given in the published page.
Build a shortlist table with the selected kit, supply, grille, cutout, required airflow and missing performance documentation. Leave the airflow cell marked “supplier data required” until a curve or test point arrives. If the project calls for a specific IP rating, mark that as a model-specific evidence field. The currently published FD9802.300 IP54 note cannot be assigned to another grille or to the complete enclosure after installation.
The same caution applies when comparing an FD filter fan with a bare RITOKS AC axial fan. Axial-fan pages do not publish enough comparable pressure-flow data to assert that one delivers more air through the same filtered cabinet. A bare fan can be a useful component in a designed ventilation path, but the filtration and ingress requirements then need their own components and evidence.
A Test Condition Checklist
Before using any quoted airflow number in a thermal calculation, confirm these inputs:
| Fråga | Varför det är viktigt |
|---|---|
| Is the value bare-fan, filtered-assembly or cabinet-system flow? | These describe different restrictions. |
| At what external static pressure was it measured? | The operating point changes with system resistance. |
| Which fan, grille and filter media were installed? | The exact configuration defines the tested path. |
| Was a matching exhaust filter included? | Outlet restriction changes the delivered flow. |
| Which supply and frequency applied? | The ordered kit must match the test condition. |
| What is the filter condition? | Clean and loaded media can differ. |
| What uncertainty or tolerance is documented? | A nominal number is not a guarantee at every point. |

The table is an evidence checklist, not a claim that RITOKS has already published each value. If no exact curve is available, the engineer can request a tested assembly point at the project's expected restriction or arrange another approved verification method. No approximate “derating factor” is supplied here because it would be ungrounded for the FD configuration.
Installation and Maintenance Affect the Result
The actual cutout should match the selected drawing, and the mounted assembly should not obstruct cabinet doors, wiring paths or service access. Seals, filter media and grilles should be installed as directed by the manufacturer. A filter that is missing or badly seated may alter airflow and ingress behavior; an improperly closed panel can change the path. The same cabinet must be reviewed in its intended operating state.
Commissioning should confirm fan rotation or flow direction as applicable, supply compatibility, control operation, filter/grille identification and a realistic temperature response under representative load. Temperature alone does not prove airflow, but it can reveal a failed ventilation concept. Establish who will inspect or replace the filter and how a blocked filter will be detected if the application requires monitoring. Avoid claiming a maintenance-free filter fan without exact evidence.
If a thermostat controls the fan, record its sensor location and switching logic. A fan that runs only at a high cabinet temperature may produce a different thermal history from a continuously running fan. The thermostat and fan must be specified together. This article does not assume an FD thermostat is included or that every fan kit has an identical controller interface.
RFQ for a Defensible Airflow Decision
Send RITOKS a complete enclosure brief:
- State cabinet dimensions, cutout limitations, installation orientation and room for intake and exhaust assemblies.
- Provide equipment heat load, normal and worst-case ambient conditions, and the target internal-temperature limit.
- State available supply and preferred FD kit/grille references, or ask for a candidate selection.
- Define required airflow at the expected system restriction, filter condition and operating scenario.
- Specify dust, water, maintenance and any enclosure ingress-protection requirements without assuming a family-wide rating.
- Request exact fan curve or tested assembly airflow, grille/filter drawings, environmental data and replacement-media information for the selected configuration.
Granska FD product family och Cabinet Cooling Fans category, then contact RITOKS with the completed brief. The practical decision is not “which fan has the largest free-air number?” It is whether the documented fan-filter-exhaust system delivers the required flow at the real cabinet operating point.
Source notes
- RITOKS FD Series filter fan och Cabinet Cooling Fans category: published kit/grille facts and explicit airflow-data gap.
- RITOKS Cabinet Cooling Fan Selection Guide: existing guide, distinct from this operating-point comparison.
- Pfannenberg filter-fan technical discussion: filter-fan/exhaust resistance principle; figures do not transfer to FD.
- Oriental Motor fan technical reference: fan pressure-flow and filter-loss explanation; no RITOKS performance data.