{"id":1785,"date":"2026-09-27T06:34:01","date_gmt":"2026-09-27T06:34:01","guid":{"rendered":"https:\/\/ritoks.com\/?p=1785"},"modified":"2026-10-04T06:58:11","modified_gmt":"2026-10-04T06:58:11","slug":"2-pole-vs-4-pole-dc-circuit-breakers","status":"publish","type":"post","link":"https:\/\/ritoks.com\/sv\/2-pole-vs-4-pole-dc-circuit-breakers\/","title":{"rendered":"2-poliga j\u00e4mf\u00f6rt med 4-poliga likstr\u00f6msbrytare: Uppbyggnad och valkriterier"},"content":{"rendered":"<p class=\"wp-block-paragraph\">Two-pole and four-pole DC circuit breakers are not simply small and large versions of the same answer. Pole count affects the permitted connection path, how conductors are disconnected and sometimes the voltage at which the complete device has documented interruption capability. The correct arrangement depends on system earthing, voltage, fault-current direction and the manufacturer&#8217;s exact wiring diagram.<\/p>\n<p class=\"wp-block-paragraph\">Denna j\u00e4mf\u00f6relse utg\u00f6r ett fr\u00e5gest\u00e4llningsunderlag f\u00f6r k\u00f6pare av likstr\u00f6ms-MCB:er. Den inneb\u00e4r inte att fyrpoliga modeller automatiskt \u00e4r s\u00e4krare eller att tv\u00e5poliga alltid \u00e4r tillr\u00e4ckliga. Klassificeringen och anslutningsuppgifterna m\u00e5ste avse den f\u00f6reslagna best\u00e4llningskoden, inte n\u00e5gon annan produkt i katalogen.<\/p>\n<h2 class=\"wp-block-heading\">B\u00f6rja med att skilja ledare fr\u00e5n brytarpoler<\/h2>\n<p class=\"wp-block-paragraph\">Ett likstr\u00f6mssystem med tv\u00e5 ledare har en positiv och en negativ ledare, men det faktumet i sig avg\u00f6r inte hur m\u00e5nga poler som beh\u00f6vs i brytaren. En tillverkare kan ange att fler \u00e4n en pol ska kopplas i serie l\u00e4ngs en ledare f\u00f6r att uppn\u00e5 en viss nominell liksp\u00e4nning. En annan l\u00f6sning kan vara att anv\u00e4nda poler i b\u00e5da ledarna. Det \u00e4r ritningen, inte ordet \u201cfyrpolig\u201d, som avg\u00f6r vad som faktiskt kopplas bort.<\/p>\n<p class=\"wp-block-paragraph\">Markera varje ledare, k\u00e4llans och lastens anslutning p\u00e5 projektets enlinjediagram. Rita sedan den f\u00f6reslagna str\u00f6mv\u00e4gen genom varje pol. Om en \u00f6verbryggningsl\u00e4nk kr\u00e4vs ska du ange om det r\u00f6r sig om ett tillverkargodk\u00e4nt tillbeh\u00f6r, en medf\u00f6ljande anslutning eller en otill\u00e5ten \u00e4ndring p\u00e5 plats. R\u00e4kna inte med externa anslutningsplintar och utg\u00e5 fr\u00e5n att varje anslutningsplint motsvarar en sj\u00e4lvst\u00e4ndigt skyddad ledare.<\/p>\n<p class=\"wp-block-paragraph\">Unders\u00f6k om brytaren \u00e4r avsedd att bryta en pol, b\u00e5da polerna eller en specificerad seriekoppling. Systemets jordning och olika felscenarier p\u00e5verkar detta beslut. En jordad ledarkonfiguration kan bed\u00f6mas p\u00e5 ett annat s\u00e4tt \u00e4n ett isolerat system; ingenj\u00f6ren m\u00e5ste till\u00e4mpa g\u00e4llande installationsregler och felanalys.<\/p>\n<h2 class=\"wp-block-heading\">J\u00e4mf\u00f6r den exakta m\u00e4rksp\u00e4nningen (likstr\u00f6m)<\/h2>\n<p class=\"wp-block-paragraph\">DC arcs do not have the natural current zero crossings of AC. Product-specific pole arrangements may therefore be used to manage interruption at higher DC voltages. Schneider Electric&#8217;s DC breaker guides show that voltage limits can depend on series-pole connections and system topology. Those examples are for Schneider products, not a universal conversion formula.<\/p>\n<p class=\"wp-block-paragraph\">Obtain the maximum operating voltage at the installation point, including charging or other high-voltage states. Compare it with the candidate&#8217;s rated DC operational voltage for the exact number of poles and connection drawing. Do not use a headline voltage from a four-pole variant to approve a two-pole variant, or vice versa.<\/p>\n<p class=\"wp-block-paragraph\">If a supplier proposes extra poles in series, request the diagram showing terminal order, polarity and links. The higher voltage claim must be explicitly documented for that exact arrangement. A user-created series bridge based on a competitor&#8217;s drawing is not evidence that the new breaker will interrupt correctly.<\/p>\n<figure data-spectra-id=\"spectra-96a848d4-6c01-437d-a10e-22bfa811add7\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" height=\"1050\" width=\"1400\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1.webp\" alt=\"Diagram \u00f6ver ledare och seriekopplade poler f\u00f6r tv\u00e5poliga och fyrpoliga likstr\u00f6msbrytare\" class=\"wp-image-1787\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-01-1-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">Antalet poler m\u00e5ste omvandlas till en dokumenterad ledare och en seriekopplad polv\u00e4g.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">Kontrollera den f\u00f6rv\u00e4ntade felstr\u00f6mmen vid samma sp\u00e4nningsniv\u00e5<\/h2>\n<p class=\"wp-block-paragraph\">A breaker must interrupt the fault available at its terminals. Provide the location-specific prospective DC fault current, not only the source&#8217;s nominal current. Batteries, converters, parallel strings and other feeds may change the duty. Compare the result with the exact candidate&#8217;s published DC breaking capacity at the relevant voltage and pole connection.<\/p>\n<p class=\"wp-block-paragraph\">The current rating and breaking capacity are different specifications. More poles do not automatically create a higher fault-current rating, and a product&#8217;s AC interrupting data cannot stand in for DC data. Ask the supplier to identify the rating table and test conditions that support the proposed connection.<\/p>\n<p class=\"wp-block-paragraph\">Se till att alla antaganden om k\u00e4llors bidrag och jordning framg\u00e5r tydligt. Om en felstudie inte \u00e4r f\u00e4rdigst\u00e4lld ska j\u00e4mf\u00f6relsen mellan brytare markeras som prelimin\u00e4r. Ink\u00f6psavdelningen kan s\u00f6ka efter l\u00e4mpliga dokument medan teknikavdelningen slutf\u00f6r ber\u00e4kningen av tillg\u00e4nglig felstr\u00f6m.<\/p>\n<h2 class=\"wp-block-heading\">G\u00e5 igenom g\u00e4llande regler f\u00f6r riktning och polaritet<\/h2>\n<p class=\"wp-block-paragraph\">Vissa likstr\u00f6msskyddsanordningar har krav p\u00e5 k\u00e4ll-\/last- eller plus-\/minus-orientering. I ett system med batteriladdning och -urladdning kan normalstr\u00f6mmen fl\u00f6da i mer \u00e4n en riktning, och felstr\u00f6mmen kan ha en ytterligare v\u00e4g. En fyrpolig konstruktion inneb\u00e4r inte att man slipper l\u00e4sa polaritetsmarkeringar och installationsanvisningar.<\/p>\n<p class=\"wp-block-paragraph\">F\u00f6r varje drift- och felstatus ska du ange vilken anslutning som \u00e4r sp\u00e4nningsf\u00f6rsedd och hur str\u00f6mmen n\u00e5r enheten. J\u00e4mf\u00f6r detta med tillverkarens exakta ritning. Om den f\u00f6reslagna brytaren beskrivs som icke-polariserad ska du kontrollera vad detta inneb\u00e4r vid den angivna sp\u00e4nningen och brytf\u00f6rm\u00e5gan; tolka inte detta som obegr\u00e4nsad dubbelriktad kapacitet.<\/p>\n<p class=\"wp-block-paragraph\">Om ritningen ger upphov till tvivel, be leverant\u00f6ren om ett skriftligt f\u00f6rtydligande kopplat till orderkoden. F\u00f6rs\u00f6k inte reda ut tvetydiga markeringar genom att prova dig fram med kopplingarna. En felaktig placering kanske inte m\u00e4rks under normal drift, men kan f\u00e5 konsekvenser vid ett felavbrott.<\/p>\n<h2 class=\"wp-block-heading\">Beakta behovet av isolering och underh\u00e5ll<\/h2>\n<p class=\"wp-block-paragraph\">Ange vilka ledare som m\u00e5ste kopplas bort f\u00f6r det avsedda underh\u00e5llet eller isolerings\u00e4ndam\u00e5let. En skyddsbrytare och en avbrytare kan ha olika godk\u00e4nda funktioner. Kontrollera om den aktuella enheten \u00e4r klassad f\u00f6r den avsedda isoleringsfunktionen och vilka delar som f\u00f6rblir sp\u00e4nningsf\u00f6rande efter att den \u00f6ppnats i den f\u00f6reslagna polkonfigurationen.<\/p>\n<p class=\"wp-block-paragraph\">Panelbyggare b\u00f6r m\u00e4rka b\u00e5da sidorna av enheten och tydligt ange anslutningarna i f\u00e4rdigritningarna. En fyrpolig enhet med tv\u00e5 poler i serie per polaritet inneb\u00e4r inte samma underh\u00e5llssituation som fyra oberoende ledare. Sk\u00e5pet och l\u00e5sningsf\u00f6rfarandet m\u00e5ste \u00e5terspegla den faktiska topologin.<\/p>\n<h2 class=\"wp-block-heading\">J\u00e4mf\u00f6r tv\u00e5poliga och fyrpoliga kandidater p\u00e5 ett r\u00e4ttvist s\u00e4tt<\/h2>\n<figure class=\"wp-block-table\"><table><thead><tr><th>Beslut<\/th><th>Tv\u00e5polig recension<\/th><th>Fyrpolig recension<\/th><\/tr><\/thead><tbody><tr><td>Anslutning<\/td><td>Vilken ledare\/ledningsv\u00e4g anv\u00e4nds f\u00f6r varje pol?<\/td><td>\u00c4r stolparna seriekopplade eller placerade p\u00e5 separata str\u00e4ckor?<\/td><\/tr><tr><td>Liksp\u00e4nning<\/td><td>Klassificering vid exakt kabeldragning<\/td><td>Klassificering vid exakt kabeldragning<\/td><\/tr><tr><td>Felhantering<\/td><td>Data om likstr\u00f6msbrytning vid den sp\u00e4nningen<\/td><td>Data om likstr\u00f6msbrytning vid den sp\u00e4nningen<\/td><\/tr><tr><td>Riktning<\/td><td>Anvisningar f\u00f6r anslutningar och polaritet<\/td><td>Anvisningar f\u00f6r anslutningar och polaritet<\/td><\/tr><tr><td>Isolering<\/td><td>Vilka ledare \u00f6ppnas?<\/td><td>Vilka ledare \u00f6ppnas?<\/td><\/tr><\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">Fyll inte i tabellen med allm\u00e4nna antaganden som \u201c2P\u201d och \u201c4P\u201d. Ange orderkoder och dokumentversioner. Om alternativen st\u00f6der olika anslutningstopologier, f\u00f6rklara detta tydligt ist\u00e4llet f\u00f6r att framst\u00e4lla ett av dem som en direkt uppgradering.<\/p>\n<figure data-spectra-id=\"spectra-34fdfcd9-b8aa-40d0-8ba9-9ee2c28afab1\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" height=\"1050\" width=\"1400\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1.webp\" alt=\"Bevismatris f\u00f6r tv\u00e5- och fyrpolig liksp\u00e4nning, brytf\u00f6rm\u00e5ga och isolering\" class=\"wp-image-1788\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-body-02-1-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">J\u00e4mf\u00f6r uppgifter om sp\u00e4nning och avbrott f\u00f6r exakt samma modell, inte enbart antalet poler.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">Konsekvenser f\u00f6r utrymme, v\u00e4rme och kabeldragning<\/h2>\n<p class=\"wp-block-paragraph\">Fyra poler kr\u00e4ver i allm\u00e4nhet st\u00f6rre fysisk bredd och kan beh\u00f6va fler l\u00e4nkar eller ledningsdragningar, men de faktiska m\u00e5tten framg\u00e5r av produktritningen. Fler str\u00f6mledande element kan ocks\u00e5 p\u00e5verka v\u00e4rmeavledningen; tillverkaren kan ange specifika krav p\u00e5 effektbegr\u00e4nsning eller installation. Kontrollera kapslingens temperatur, n\u00e4rliggande enheter, utrymmet f\u00f6r samlingsskenor eller kabelanslutningar samt monteringsriktningen.<\/p>\n<p class=\"wp-block-paragraph\">Ett kompakt tv\u00e5poligt alternativ b\u00f6r inte v\u00e4ljas enbart f\u00f6r att spara utrymme i skenan om dess dokumenterade liksp\u00e4nning eller anslutningskapacitet \u00e4r otillr\u00e4cklig. P\u00e5 samma s\u00e4tt b\u00f6r en st\u00f6rre fyrpolig enhet inte v\u00e4ljas utan att man f\u00f6rst har kontrollerat dess kopplingsschema och termiska konsekvenser. Det b\u00e4sta alternativet \u00e4r den godk\u00e4nda elektriska kopplingen som kan installeras och underh\u00e5llas p\u00e5 r\u00e4tt s\u00e4tt.<\/p>\n<h2 class=\"wp-block-heading\">Dokumentera varje k\u00e4lla till p\u00e5st\u00e5endet om betygs\u00e4ttningen<\/h2>\n<p class=\"wp-block-paragraph\">En tillf\u00f6rlitlig j\u00e4mf\u00f6relse b\u00f6r ange exakt vilket datablad det g\u00e4ller, dess version, vilken sida som inneh\u00e5ller tabellen \u00f6ver likstr\u00f6msv\u00e4rden samt installationsritningen som visar motsvarande anslutningsv\u00e4g. F\u00f6rvara dessa dokument tillsammans. En m\u00e4rktabell utan anslutningsschema, eller ett anslutningsschema utan uppgifter om brytkapacitet, inneb\u00e4r en viktig brist. K\u00f6pare b\u00f6r be leverant\u00f6rerna att ange vilken f\u00f6reslagen best\u00e4llningskod varje sida avser.<\/p>\n<p class=\"wp-block-paragraph\">Om en enhet i offerten har flera angivna sp\u00e4nningar, ska du ta reda p\u00e5 om dessa motsvarar olika polantal, seriekopplingar, jordningssystem eller testf\u00f6rh\u00e5llanden. Sammanfoga inte de mest f\u00f6rdelaktiga v\u00e4rdena till en sammansatt specifikation. J\u00e4mf\u00f6relsen b\u00f6r \u00e4ven ange eventuella tillbeh\u00f6r eller fabriksanslutningar som kr\u00e4vs f\u00f6r att realisera den testade konfigurationen. Ett l\u00e5gt enhetspris kan vara missvisande om s\u00e4rskilda anslutningar, ett st\u00f6rre h\u00f6lje eller ytterligare kabeldragning kr\u00e4vs.<\/p>\n<p class=\"wp-block-paragraph\">Vid konstruktionsgranskningen b\u00f6r n\u00e5gon annan \u00e4n den som ritat ritningarna rita upp den aktuella ledningsv\u00e4gen p\u00e5 b\u00e5da ritningarna. Denna oberoende kontroll kan uppt\u00e4cka en saknad brygga eller en ledare som \u00e4r ansluten till fel anslutningspunkt innan enheten monteras. Resultatet b\u00f6r dokumenteras som en topologikontroll, separat fr\u00e5n sp\u00e4nnings- och felstr\u00f6msber\u00e4kningarna.<\/p>\n<h2 class=\"wp-block-heading\">Vad ska man bifoga i en j\u00e4mf\u00f6rande offertf\u00f6rfr\u00e5gan<\/h2>\n<p class=\"wp-block-paragraph\">Skicka information om systemets enledningsanslutning, sp\u00e4nningsf\u00f6rlopp, jordningskonfiguration, felstr\u00f6msv\u00e4rden, f\u00f6rv\u00e4ntade str\u00f6mriktningar, ledare som ska kopplas bort samt utrymmesbegr\u00e4nsningar i elsk\u00e5pet. Be leverant\u00f6ren om exakta best\u00e4llningskoder f\u00f6r tv\u00e5poliga och fyrpoliga enheter, tabeller \u00f6ver likstr\u00f6msv\u00e4rden, kopplingsscheman, anvisningar om polaritet, brytdata och installationskrav.<\/p>\n<p class=\"wp-block-paragraph\">Den <a href=\"https:\/\/ritoks.com\/sv\/product-category\/dc-power-protection\/dc-circuit-breakers\/dc-miniature-circuit-breakers\/\">DC-MCB-kategori<\/a> ger en aff\u00e4rsm\u00e4ssig kontext. Den <a href=\"https:\/\/ritoks.com\/sv\/products\/2p-dc-miniature-circuit-breaker-500-1000v-6-63a\/\">serie med tv\u00e5poliga likstr\u00f6ms-MCB:er<\/a> och <a href=\"https:\/\/ritoks.com\/sv\/products\/high-current-dc-miniature-circuit-breaker-12-125v-63-250a\/\">serie av likstr\u00f6ms-MCB:er f\u00f6r h\u00f6gre str\u00f6mstyrka<\/a> \u00e4r utg\u00e5ngspunkter, inte bevis f\u00f6r att det finns ett specifikt fyrpoligt alternativ eller att n\u00e5got av dem passar till\u00e4mpningen.<\/p>\n<p class=\"wp-block-paragraph\">Anv\u00e4ndning <a href=\"https:\/\/ritoks.com\/sv\/contact-us\/\">Kontakt med RITOKS<\/a> f\u00f6r att beg\u00e4ra modellspecifika dokument. Om det f\u00f6reslagna antalet stolpar medf\u00f6r \u00e4ndringar i panelritningen, ska valet skickas tillbaka till konstruktionsavdelningen innan best\u00e4llning g\u00f6rs. Spara det slutgiltiga anslutningsschemat tillsammans med materialf\u00f6rteckningen f\u00f6r kontroll och eventuella framtida utbyten.<\/p>\n<h2 class=\"wp-block-heading\">Vanliga fr\u00e5gor<\/h2>\n<h3 class=\"wp-block-heading\">\u00c4r en fyrpolig likstr\u00f6msbrytare alltid b\u00e4ttre?<\/h3>\n<p class=\"wp-block-paragraph\">Nej. Den kan visserligen st\u00f6dja ett annat, av tillverkaren godk\u00e4nt anslutnings- eller fr\u00e5nkopplingssyfte, men l\u00e4mpligheten beror p\u00e5 den exakta sp\u00e4nningen, felfrekvensen, ledningsdragningen och systemets utformning.<\/p>\n<h3 class=\"wp-block-heading\">Betyder \u201dtv\u00e5polig\u201d att b\u00e5da polariteterna \u00e4r skyddade?<\/h3>\n<p class=\"wp-block-paragraph\">Inte n\u00f6dv\u00e4ndigtvis. Polerna kan vara seriekopplade p\u00e5 en ledning i en dokumenterad konfiguration. L\u00e4s det aktuella schemat och ta reda p\u00e5 vilka ledare som faktiskt bryts.<\/p>\n<h3 class=\"wp-block-heading\">Kan stolpar kopplas samman ute p\u00e5 f\u00e4ltet f\u00f6r att uppn\u00e5 en h\u00f6gre m\u00e4rkbelastning?<\/h3>\n<p class=\"wp-block-paragraph\">Endast om tillverkarens dokumentation uttryckligen till\u00e5ter anslutningen, anger vilka anslutningar som kr\u00e4vs och specificerar den resulterande m\u00e4rkprestandan. Dra aldrig slutsatser utifr\u00e5n en annan produkt.<\/p>\n<h2 class=\"wp-block-heading\">Sammanfattning<\/h2>\n<p class=\"wp-block-paragraph\">Choose a DC breaker pole arrangement by mapping the system conductors and fault paths to the manufacturer&#8217;s exact connection diagram. Then verify voltage, DC breaking capacity, polarity and isolation requirements for that arrangement. Pole count is a starting question, not a rating.<\/p>\n<h2 class=\"wp-block-heading\">K\u00e4llor<\/h2>\n<ul class=\"wp-block-list\"><li><a href=\"https:\/\/library.e.abb.com\/public\/da3ed0fd2ecc4c92931126492e57e00a\/1SXU400208C0201_ABB%20MCB%20CT_DGT.pdf\" target=\"_blank\" rel=\"noopener\">ABB, S200UDC miniatyrbrytare \u2013 anslutningsscheman f\u00f6r likstr\u00f6msapplikationer<\/a>.<\/li><li><a href=\"https:\/\/www.se.com\/us\/en\/download\/document\/CA908061E\/\" target=\"_blank\" rel=\"noopener\">Schneider Electric \u2013 Guide f\u00f6r val av likstr\u00f6msbrytare och polanslutning<\/a>.<\/li><li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66277\" target=\"_blank\" rel=\"noopener\">IEC, IEC 60947-2:2024 str\u00f6mbrytare<\/a>.<\/li><\/ul>","protected":false},"excerpt":{"rendered":"<p>Compare two- and four-pole DC breakers through conductor paths, manufacturer wiring diagrams, voltage and fault-interruption evidence.<\/p>","protected":false},"author":1,"featured_media":1786,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":"viox","ritoks_resource_product_cat_term_id":125,"footnotes":""},"categories":[64],"tags":[],"class_list":["post-1785","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-circuit-protection"],"acf":[],"spectra_blocks_featured_image_url":{"thumbnail":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-150x150.webp","width":150,"height":150},"medium":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-300x169.webp","width":300,"height":169},"medium_large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-768x432.webp","width":768,"height":432},"large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1-1024x576.webp","width":1024,"height":576},"full":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/2-pole-vs-4-pole-dc-circuit-breakers-hero-01-1.webp","width":1600,"height":900}},"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/sv\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/posts\/1785","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/comments?post=1785"}],"version-history":[{"count":2,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/posts\/1785\/revisions"}],"predecessor-version":[{"id":2157,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/posts\/1785\/revisions\/2157"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/media\/1786"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/media?parent=1785"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/categories?post=1785"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/sv\/wp-json\/wp\/v2\/tags?post=1785"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}