{"id":734,"date":"2026-09-06T07:09:34","date_gmt":"2026-09-06T07:09:34","guid":{"rendered":"https:\/\/ritoks.com\/?p=734"},"modified":"2026-10-11T00:44:32","modified_gmt":"2026-10-11T00:44:32","slug":"rack-pdu-selection-guide","status":"publish","type":"post","link":"https:\/\/ritoks.com\/tr\/rack-pdu-selection-guide\/","title":{"rendered":"Raf PDU Se\u00e7im K\u0131lavuzu: Priz Say\u0131s\u0131, Gerilim, Fi\u015f ve Priz Tipi"},"content":{"rendered":"\n<div class=\"wp-block-group alignfull has-ast-global-color-5-background-color has-background is-layout-constrained wp-container-core-group-is-layout-1079f00e wp-block-group-is-layout-constrained\" style=\"padding-top:56px;padding-right:24px;padding-bottom:48px;padding-left:24px\">\n<h1 class=\"wp-block-heading\">Rack PDU Selection Guide: Outlet Count, Voltage, Plug and Socket Format<\/h1>\n\n<p class=\"has-medium-font-size wp-block-paragraph\">Selecting a rack power distribution unit involves more than counting outlets.<\/p>\n\n<p class=\"wp-block-paragraph\">A buyer may need to compare:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>input voltage<\/li>\n\n\n<li>rated current<\/li>\n\n\n<li>input plug or connector<\/li>\n\n\n<li>output socket format<\/li>\n\n\n<li>outlet count<\/li>\n\n\n<li>rack format<\/li>\n\n\n<li>cord or input arrangement<\/li>\n\n\n<li>physical constraints<\/li>\n\n\n<li>required documentation<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">These parameters describe different parts of the PDU specification and should not be treated as interchangeable.<\/p>\n\n<p class=\"wp-block-paragraph\">Raritan\u2019s <a href=\"https:\/\/cdn.raritan.com\/download\/web\/iPDU-Handbook-Digital-V1195.pdf\" target=\"_blank\" rel=\"noopener\">official rack PDU selection guidance<\/a> similarly identifies factors such as voltage, current, input plug type, number and type of outlets, rack units and physical dimensions as important configuration variables.<\/p>\n\n<p class=\"wp-block-paragraph\">The key sourcing principle is simple:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Start with the requirements already defined for the rack or project, then compare those requirements with the exact published PDU configuration.<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">Do not assume that a supplier can determine the correct electrical design from server count or rack size alone.<\/p>\n\n<figure data-spectra-id=\"spectra-2e9c8c8a-01b0-4967-87e1-79974e4ac6bb\" class=\"wp-block-image size-full has-custom-border\" ><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection.jpg\" width=\"1536\" height=\"1024\" alt=\"Rack PDU and server rack inspection in a data center environment\" class=\"wp-image-736\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection.jpg 1536w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection-600x400.jpg 600w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection-300x200.jpg 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection-1024x683.jpg 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-server-rack-inspection-768x512.jpg 768w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption class=\"wp-element-caption\">Illustrative rack PDU procurement and specification-review environment.<\/figcaption><\/figure>\n<\/div>\n\n\n\n<div class=\"wp-block-group is-layout-constrained wp-container-core-group-is-layout-5a87b4ec wp-block-group-is-layout-constrained\" style=\"padding-top:40px;padding-right:24px;padding-bottom:24px;padding-left:24px\">\n<h2 class=\"wp-block-heading\">Contents<\/h2>\n\n<ul class=\"wp-block-list\">\n<li><a href=\"#selection-checklist\">Rack PDU selection checklist<\/a><\/li>\n\n\n<li><a href=\"#required-voltage\">Voltage and current<\/a><\/li>\n\n\n<li><a href=\"#input-output\">Input plug and output socket<\/a><\/li>\n\n\n<li><a href=\"#outlet-count\">Outlet count and capacity<\/a><\/li>\n\n\n<li><a href=\"#rack-format\">Rack format and physical constraints<\/a><\/li>\n\n\n<li><a href=\"#optional-features\">Optional feature terminology<\/a><\/li>\n\n\n<li><a href=\"#ritoks-families\">Current RITOKS rack power families<\/a><\/li>\n\n\n<li><a href=\"#common-mistakes\">Common selection mistakes<\/a><\/li>\n\n\n<li><a href=\"#inquiry-checklist\">Inquiry checklist<\/a><\/li>\n\n\n<li><a href=\"#faq\">FAQ<\/a><\/li>\n<\/ul>\n<\/div>\n\n\n\n<div class=\"wp-block-group is-layout-constrained wp-container-core-group-is-layout-3ebe37c8 wp-block-group-is-layout-constrained\" style=\"padding-top:32px;padding-right:24px;padding-bottom:56px;padding-left:24px\">\n<h2 class=\"wp-block-heading\" id=\"selection-checklist\">Rack PDU Selection Checklist<\/h2>\n\n<figure class=\"wp-block-table is-style-stripes\"><table class=\"has-fixed-layout\"><thead><tr><th>Parameter<\/th><th>What the Buyer Should Specify<\/th><th>Why It Matters<\/th><\/tr><\/thead><tbody><tr><td>Voltage<\/td><td>Required input voltage<\/td><td>PDU families may be built for different voltage ratings<\/td><\/tr><tr><td>Current<\/td><td>Required rated current<\/td><td>Current capability differs by model<\/td><\/tr><tr><td>Input plug<\/td><td>Required plug or connector<\/td><td>Determines how the PDU connects to the upstream supply<\/td><\/tr><tr><td>Output socket<\/td><td>Required outlet\/receptacle format<\/td><td>Must match connected equipment<\/td><\/tr><tr><td>Outlet count<\/td><td>Number of required outputs<\/td><td>Product families differ significantly in outlet quantity<\/td><\/tr><tr><td>Rack format<\/td><td>1U or other required format<\/td><td>Affects physical installation<\/td><\/tr><tr><td>Cord \/ input arrangement<\/td><td>Required cable length, cord or no-cord format<\/td><td>May vary by product configuration<\/td><\/tr><tr><td>Documentation<\/td><td>Required drawings, specifications or evidence<\/td><td>Availability depends on exact model and variant<\/td><\/tr><\/tbody><\/table><\/figure>\n\n<figure data-spectra-id=\"spectra-c90bef09-d0f9-4331-97ac-3e559904d4a1\" class=\"wp-block-image size-full has-custom-border\" ><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs.jpg\" width=\"1536\" height=\"1024\" alt=\"Key rack PDU selection inputs including voltage current plug socket outlet count and rack format\" class=\"wp-image-737\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs.jpg 1536w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs-600x400.jpg 600w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs-300x200.jpg 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs-1024x683.jpg 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/09\/rack-pdu-selection-inputs-768x512.jpg 768w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption class=\"wp-element-caption\">Key buyer-supplied inputs for comparing rack PDU configurations.<\/figcaption><\/figure>\n\n<p class=\"wp-block-paragraph\">Not every RFQ needs every item, but leaving out basic configuration data can make product matching much slower.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"required-voltage\">1. Start With the Required Voltage<\/h2>\n\n<p class=\"wp-block-paragraph\">Voltage is one of the first parameters to confirm.<\/p>\n\n<p class=\"wp-block-paragraph\">Current RITOKS rack-power products include different published voltage configurations.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU-US8-15A<\/h3>\n\n<p class=\"wp-block-paragraph\">The assembled configuration currently publishes:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>AC 125V<\/li>\n\n\n<li>15A<\/li>\n\n\n<li>1875W<\/li>\n\n\n<li>eight grounded US-style three-slot outlets<\/li>\n<\/ul>\n\n<h3 class=\"wp-block-heading\">RTS-PDU1U-10A<\/h3>\n\n<p class=\"wp-block-paragraph\">The current published configuration lists:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>AC 250V<\/li>\n\n\n<li>10A<\/li>\n\n\n<li>2500W<\/li>\n\n\n<li>1U rack format<\/li>\n\n\n<li>multiple outlet-count options<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">These values describe two different product families; see the <a href=\"https:\/\/ritoks.com\/125v-8-outlet-vs-250v-1u-rack-pdu\/\">125V 8-outlet and 250V 1U rack PDU comparison<\/a> for a model-specific side-by-side view.<\/p>\n\n<p class=\"wp-block-paragraph\">They should not be converted into universal rules such as:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>125V is always the correct choice for US racks<\/li>\n\n\n<li>250V is always the correct choice for international racks<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">The buyer should provide the voltage required by the actual project.<\/p>\n\n<p class=\"wp-block-paragraph\">A useful inquiry field is:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Required input voltage: [project voltage]<\/p>\n<\/blockquote>\n\n<h2 class=\"wp-block-heading\" id=\"rated-current\">2. Confirm the Rated Current<\/h2>\n\n<p class=\"wp-block-paragraph\">Voltage and current should be checked separately.<\/p>\n\n<p class=\"wp-block-paragraph\">A PDU may have the correct voltage but still not match the required current specification.<\/p>\n\n<p class=\"wp-block-paragraph\">Current published RITOKS examples include:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>RTS-PDU-US8-15A \u2014 15A<\/li>\n\n\n<li>RTS-PDU1U-10A \u2014 10A<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Product 253, RTS-PDUSM, includes individual modular components with designations such as 10A and 16A, but it is a component family rather than a complete assembled PDU.<\/p>\n\n<p class=\"wp-block-paragraph\">That distinction matters.<\/p>\n\n<p class=\"wp-block-paragraph\">A 16A component option should not automatically be interpreted as proof of a complete 16A rack PDU configuration.<\/p>\n\n<p class=\"wp-block-paragraph\">For sourcing, provide:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Required current: [project requirement]<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">rather than asking the supplier to calculate the PDU current from the number of servers alone.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"input-output\">3. Separate Input Plug From Output Socket<\/h2>\n\n<p class=\"wp-block-paragraph\">One of the easiest PDU sourcing mistakes is mixing up the input connection and the output receptacles.<\/p>\n\n<p class=\"wp-block-paragraph\">They perform different roles.<\/p>\n\n<h3 class=\"wp-block-heading\">Input Plug or Connector<\/h3>\n\n<p class=\"wp-block-paragraph\">This is how the PDU receives power from the upstream supply.<\/p>\n\n<h3 class=\"wp-block-heading\">Output Socket or Receptacle<\/h3>\n\n<p class=\"wp-block-paragraph\">These are the connections used by the equipment powered from the PDU.<\/p>\n\n<p class=\"wp-block-paragraph\">The same PDU specification may therefore involve two different connector questions:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">What does the PDU plug into?<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">and:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">What plugs into the PDU?<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">Raritan\u2019s product-selection tools treat plug type and outlet configuration as separate PDU parameters, which reflects this distinction.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"input-plug\">4. Check the Input Plug or Connector Requirement<\/h2>\n\n<p class=\"wp-block-paragraph\">Current RITOKS evidence is stronger for modular input-component options than for the two assembled PDU families.<\/p>\n\n<p class=\"wp-block-paragraph\">RTS-PDUSM currently lists input or connector options including:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>China 10A \/ 16A<\/li>\n\n\n<li>European<\/li>\n\n\n<li>UK<\/li>\n\n\n<li>US<\/li>\n\n\n<li>Australian<\/li>\n\n\n<li>Italian<\/li>\n\n\n<li>IEC C13<\/li>\n\n\n<li>IEC C14<\/li>\n\n\n<li>IEC C19<\/li>\n\n\n<li>IEC C20<\/li>\n\n\n<li>16A \/ 32A industrial options<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">However, these are part of a modular component family.<\/p>\n\n<p class=\"wp-block-paragraph\">They do not prove that every option is available in every assembled PDU combination.<\/p>\n\n<p class=\"wp-block-paragraph\">For RTS-PDU-US8-15A and RTS-PDU1U-10A, the exact input plug is not currently published.<\/p>\n\n<p class=\"wp-block-paragraph\">So a buyer should specify:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Required input plug \/ connector: [type]<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">and request exact variant confirmation.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"output-socket\">5. Choose the Required Output Socket Format<\/h2>\n\n<p class=\"wp-block-paragraph\">Output receptacles need to match the equipment being connected.<\/p>\n\n<p class=\"wp-block-paragraph\">The broader rack-PDU market uses several output formats, including IEC 60320 C13 and C19 receptacles. <a href=\"https:\/\/www.se.com\/us\/en\/product\/AP8441\/rack-pdu-2g-meteredbyoutlet-zerou-30a-200-208v-21-c13-3-c19\/\" target=\"_blank\" rel=\"noopener\">Official Schneider Electric rack PDU product documentation<\/a>, for example, explicitly identifies products with C13 and C19 output receptacles.<\/p>\n\n<p class=\"wp-block-paragraph\">IEC 60320-1 provides the general standard framework for appliance couplers used to connect electrical equipment to the mains supply.<\/p>\n\n<p class=\"wp-block-paragraph\">For RITOKS, however, the current evidence must remain more limited.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDUSM<\/h3>\n\n<p class=\"wp-block-paragraph\">Published component options include:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>universal outlet modules<\/li>\n\n\n<li>China-standard modules<\/li>\n\n\n<li>US-style modules<\/li>\n\n\n<li>C13 modules<\/li>\n\n\n<li>C19 modules<\/li>\n\n\n<li>C13 slide-lock modules<\/li>\n\n\n<li>SPD modules<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">These are modular socket components.<\/p>\n\n<p class=\"wp-block-paragraph\">They should not be described as proof that RITOKS currently offers a complete assembled C13\/C19 rack PDU.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU-US8-15A<\/h3>\n\n<p class=\"wp-block-paragraph\">Current assembled output configuration:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>eight grounded US-style three-slot outlets<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Exact NEMA designation is not published.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU1U-10A<\/h3>\n\n<p class=\"wp-block-paragraph\">Current assembled configuration publishes:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>three-slot outlets<\/li>\n\n\n<li>multiple outlet-count variants<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">The exact regional outlet standard is not currently confirmed.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"outlet-count\">6. Decide How Many Outlets Are Needed<\/h2>\n\n<p class=\"wp-block-paragraph\">Outlet count is one of the most visible differences between rack PDU configurations.<\/p>\n\n<p class=\"wp-block-paragraph\">Current RITOKS published options include:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>RTS-PDU-US8-15A<\/li>\n\n\n<li>8 outlets<\/li>\n\n\n<li>RTS-PDU1U-10A<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Available published counts include:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>2<\/li>\n\n\n<li>3<\/li>\n\n\n<li>4<\/li>\n\n\n<li>5<\/li>\n\n\n<li>6<\/li>\n\n\n<li>7<\/li>\n\n\n<li>8<\/li>\n\n\n<li>10<\/li>\n\n\n<li>12<\/li>\n\n\n<li>14<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">This gives buyers a meaningful range to compare.<\/p>\n\n<p class=\"wp-block-paragraph\">But higher outlet count is not automatically better.<\/p>\n\n<p class=\"wp-block-paragraph\">Outlet count does not tell you:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>required electrical capacity<\/li>\n\n\n<li>upstream circuit capability<\/li>\n\n\n<li>rack power budget<\/li>\n\n\n<li>whether every outlet will be used simultaneously<\/li>\n\n\n<li>future power demand<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Those belong to the broader rack electrical design.<\/p>\n\n<p class=\"wp-block-paragraph\">For an RFQ, the safer field is simply:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Required outlet count: [number]<\/p>\n<\/blockquote>\n\n<h2 class=\"wp-block-heading\" id=\"outlet-capacity\">7. Outlet Count and Electrical Capacity Are Different Questions<\/h2>\n\n<p class=\"wp-block-paragraph\">A 14-outlet PDU is not automatically a higher-capacity PDU than an 8-outlet unit.<\/p>\n\n<p class=\"wp-block-paragraph\">Outlet count describes the number of connection points.<\/p>\n\n<p class=\"wp-block-paragraph\">Voltage, current and rated power describe different electrical characteristics.<\/p>\n\n<p class=\"wp-block-paragraph\">For example, the current RITOKS data includes:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>RTS-PDU-US8-15A \u2014 8 outlets, 125V, 15A, 1875W<\/li>\n\n\n<li>RTS-PDU1U-10A \u2014 up to 14 outlets, 250V, 10A, 2500W<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">These specifications should be read together rather than ranking the products by outlet count alone.<\/p>\n\n<p class=\"wp-block-paragraph\">The final rack load requirement must come from the actual electrical design.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"rack-format\">8. Check Rack Format and Physical Constraints<\/h2>\n\n<p class=\"wp-block-paragraph\">Rack installation format affects how the PDU fits into the cabinet.<\/p>\n\n<p class=\"wp-block-paragraph\">The wider rack PDU market includes both horizontal rack-unit formats and vertical zero-U designs. <a href=\"https:\/\/www.eaton.com\/content\/dam\/eaton\/products\/backup-power-ups-surge-it-power-distribution\/power-distribution-for-it-equipment\/eaton-rack-pdu-buying-guide-MZ155005EN.pdf\" target=\"_blank\" rel=\"noopener\">Eaton describes common formats including 1U horizontal and 0U vertical PDUs<\/a>, while also noting that mounting choice depends on available rack space and deployment needs.<\/p>\n\n<p class=\"wp-block-paragraph\">For current RITOKS products:<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU1U-10A<\/h3>\n\n<p class=\"wp-block-paragraph\">1U is confirmed.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU-US8-15A<\/h3>\n\n<p class=\"wp-block-paragraph\">Rack orientation and exact format are currently not confirmed.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDUSM<\/h3>\n\n<p class=\"wp-block-paragraph\">This is a component family, so rack format is not published.<\/p>\n\n<p class=\"wp-block-paragraph\">RITOKS currently does not have a confirmed 0U PDU in the reviewed product set.<\/p>\n\n<p class=\"wp-block-paragraph\">Therefore, do not interpret general industry 0U terminology as evidence of a RITOKS 0U product.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"one-u-limitations\">9. Do Not Assume \u201c1U\u201d Automatically Means Every Physical Detail<\/h2>\n\n<p class=\"wp-block-paragraph\">The 1U designation provides useful rack-height information, but a buyer may still need more data.<\/p>\n\n<p class=\"wp-block-paragraph\">Depending on the project, ask for:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>exact overall dimensions<\/li>\n\n\n<li>mounting-hole arrangement<\/li>\n\n\n<li>rack ears or mounting hardware<\/li>\n\n\n<li>terminal position<\/li>\n\n\n<li>cable-entry direction<\/li>\n\n\n<li>available clearance<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">For RTS-PDU1U-10A, 1U is published, but exact horizontal\/vertical wording, mounting drawing and detailed dimensions are not currently published.<\/p>\n\n<p class=\"wp-block-paragraph\">So the article should not turn \u201c1U\u201d into a complete mechanical specification.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"cable-arrangement\">10. Check the Cable or Input Arrangement<\/h2>\n\n<p class=\"wp-block-paragraph\">Cord configuration can also differ between PDU variants.<\/p>\n\n<p class=\"wp-block-paragraph\">Current RITOKS evidence includes:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>RTS-PDU-US8-15A<\/li>\n\n\n<li>1.8 m cable on the assembled configuration<\/li>\n\n\n<li>RTS-PDU1U-10A<\/li>\n\n\n<li>2 m cord option<\/li>\n\n\n<li>no-cord variant<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">That makes cable configuration a useful RFQ field.<\/p>\n\n<p class=\"wp-block-paragraph\">A buyer can specify:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Cord requirement: [length \/ no-cord \/ connector requirement]<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">Exact plug compatibility still needs confirmation where the product page does not publish the input plug.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"optional-features\">11. Understand Optional Features Without Assuming Them<\/h2>\n<p class=\"wp-block-paragraph\">Rack PDU names can describe different layers of a power-distribution system. Before comparing suppliers, separate how power is distributed, where it is measured, whether it can be observed remotely, and whether an operator can switch an outlet remotely. An ATS adds a separate question about the availability of two input sources.<\/p>\n<figure class=\"wp-block-table\"><table><thead><tr><th>Term<\/th><th>Buyer requirement<\/th><th>Confirm for the quoted variant<\/th><\/tr><\/thead><tbody><tr><td>Basic PDU<\/td><td>Rack-level distribution and outlet arrangement<\/td><td>Input and outlet ratings, connector, mounting and documents<\/td><\/tr><tr><td>Metered PDU<\/td><td>Measurement at a stated point<\/td><td>Inlet, branch or outlet level; display and reporting method<\/td><\/tr><tr><td>Monitored PDU<\/td><td>Remote visibility of measurements, alarms or status<\/td><td>Interface, protocol, alarm events, access and data retention<\/td><\/tr><tr><td>Switched PDU<\/td><td>Remote control of outlets or outlet groups<\/td><td>Control scope, permissions, sequencing, recovery and local override<\/td><\/tr><tr><td>ATS PDU<\/td><td>Transfer between two available input sources<\/td><td>Source requirements, transfer behavior and maintenance procedure<\/td><\/tr><\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">The terms \u201csmart\u201d and \u201cmanaged\u201d vary between suppliers. Request a function list covering measurement, network access and switching separately. <a href=\"https:\/\/www.vertiv.com\/en-emea\/insights\/articles\/educational-articles\/what-is-a-rack-pdu\/\" target=\"_blank\" rel=\"noopener\">Vertiv\u2019s rack PDU overview<\/a> distinguishes local metering, remote monitoring and outlet switching. <a href=\"https:\/\/www.eaton.com\/us\/en-us\/catalog\/backup-power-ups-surge-it-power-distribution\/eaton-metered-outlet-rack-pdu.html\" target=\"_blank\" rel=\"noopener\">Eaton\u2019s outlet-metered family<\/a> illustrates why the measurement location must be specified. These sources describe industry functions, not RITOKS model capabilities.<\/p>\n<h3 class=\"wp-block-heading\">Local switching and remote outlet control<\/h3>\n<p class=\"wp-block-paragraph\">A local master switch and remote outlet control solve different operating problems. Remote restart requires a control path, a defined outlet or group, permission behavior and documented response after power or communication loss. State that requirement explicitly in the RFQ.<\/p>\n<h3 class=\"wp-block-heading\">Specify the measurement point<\/h3>\n<p class=\"wp-block-paragraph\">\u201cMetered\u201d should be followed by the measurement location. Inlet metering can show total PDU input, while outlet-level metering associates readings with individual equipment. Ask for the measurement layer, display, alarms, data access and supporting document.<\/p>\n<h3 class=\"wp-block-heading\">Define the source-transfer requirement separately<\/h3>\n<p class=\"wp-block-paragraph\">An ATS transfers a connected load between available input sources. Battery-backed runtime must come from an upstream UPS or another documented backup source. Verify transfer performance against the connected equipment\u2019s tolerance. See <a href=\"https:\/\/www.se.com\/ie\/en\/faqs\/FA156201\/\" target=\"_blank\" rel=\"noopener\">Schneider\u2019s rack ATS application guidance<\/a>.<\/p>\n<ul class=\"wp-block-list\"><li>Required measurement: [none \/ inlet \/ branch \/ outlet]<\/li><li>Remote control scope: [none \/ group \/ individual outlet]<\/li><li>Required protocol or interface: [project requirement]<\/li><li>Power-loss and communication-loss behavior: [supplier to document]<\/li><li>Two source conditions and transfer trigger: [supplier to document]<\/li><\/ul><h2 class=\"wp-block-heading\" id=\"surge-language\">12. Be Careful With Surge-Protection Language<\/h2>\n\n<p class=\"wp-block-paragraph\">Two current product families include limited surge-related information.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDU-US8-15A<\/h3>\n\n<p class=\"wp-block-paragraph\">The product is supplier-described as having a surge-protected switch.<\/p>\n\n<p class=\"wp-block-paragraph\">However, detailed surge rating and test evidence are still pending.<\/p>\n\n<h3 class=\"wp-block-heading\">RTS-PDUSM<\/h3>\n\n<p class=\"wp-block-paragraph\">A modular SPD option is listed.<\/p>\n\n<p class=\"wp-block-paragraph\">Again, exact electrical and surge parameters are not currently published.<\/p>\n\n<p class=\"wp-block-paragraph\">Therefore, buyers can ask:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Surge-protection requirement: [project requirement]<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">but the supplier should confirm exact performance documentation before any technical claim is made.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"ritoks-families\">Current RITOKS Rack Power Families<\/h2>\n\n<figure class=\"wp-block-table is-style-stripes\"><table class=\"has-fixed-layout\"><thead><tr><th>Product Family<\/th><th>Published Role<\/th><th>Key Confirmed Data<\/th><th>Important Limitations<\/th><\/tr><\/thead><tbody><tr><td>RTS-PDUSM<\/td><td>Modular PDU socket\/input component family<\/td><td>Regional socket modules, C13\/C19 options, multiple input\/connector options<\/td><td>Not an assembled PDU; exact voltage, rack format and assembled combinations not published<\/td><\/tr><tr><td>RTS-PDU-US8-15A<\/td><td>Assembled 8-outlet PDU<\/td><td>125V, 15A, 1875W, 8 US-style outlets, 1.8m cable<\/td><td>Exact input plug, NEMA designation, rack format and verified surge parameters not published<\/td><\/tr><tr><td>RTS-PDU1U-10A<\/td><td>Configurable-outlet-count 1U PDU<\/td><td>250V, 10A, 2500W, 1U, 2\u201314 outlet variants, 2m\/no-cord options, double-pole master switch<\/td><td>Exact input plug and regional socket standard not published; no 0U, metering or remote switching confirmed<\/td><\/tr><\/tbody><\/table><\/figure>\n\n<div class=\"wp-block-columns is-layout-flex wp-container-core-columns-is-layout-fe5038c6 wp-block-columns-is-layout-flex\" style=\"margin-top:32px;margin-bottom:32px\">\n<div class=\"wp-block-column is-layout-flow wp-block-column-is-layout-flow\">\n<figure data-spectra-id=\"spectra-f9edb525-fd58-43bb-b2b5-cae9423cdcc9\" class=\"wp-block-image size-full has-custom-border\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib.jpg\" width=\"800\" height=\"800\" alt=\"RTS-PDUSM modular PDU socket and input components\" class=\"wp-image-255\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib.jpg 800w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib-300x300.jpg 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib-100x100.jpg 100w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib-600x600.jpg 600w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib-150x150.jpg 150w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01gyt77R2CuAbzr2IU5_2213342278533-0-cib-768x768.jpg 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/figure>\n\n<h3 class=\"wp-block-heading\"><a href=\"https:\/\/ritoks.com\/products\/modular-pdu-outlet-socket-components-c13-c19-regional-options\/\">RTS-PDUSM Modular PDU Components<\/a><\/h3>\n\n<p class=\"has-small-font-size wp-block-paragraph\" style=\"font-weight:700\">COMPONENT FAMILY \u2014 NOT ASSEMBLED PDU<\/p>\n\n<p class=\"wp-block-paragraph\">Modular socket and input component family.<\/p>\n<\/div>\n\n<div class=\"wp-block-column is-layout-flow wp-block-column-is-layout-flow\">\n<figure data-spectra-id=\"spectra-72440919-f36b-449c-bbe5-8b93b726dbba\" class=\"wp-block-image size-full has-custom-border\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_.webp\" width=\"750\" height=\"750\" alt=\"RTS-PDU-US8-15A 8-outlet rack PDU\" class=\"wp-image-261\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_.webp 750w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_-300x300.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_-100x100.webp 100w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_-600x600.webp 600w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/O1CN01VIdWUe1gjZZKk5R0W_953674178-0-cib.jpg_-150x150.webp 150w\" sizes=\"auto, (max-width: 750px) 100vw, 750px\" \/><\/figure>\n\n<h3 class=\"wp-block-heading\"><a href=\"https:\/\/ritoks.com\/products\/8-outlet-us-rack-pdu-15a-125v-surge-protected-switch\/\">RTS-PDU-US8-15A 8-Outlet Rack PDU<\/a><\/h3>\n\n<p class=\"wp-block-paragraph\">125V \/ 15A assembled 8-outlet PDU.<\/p>\n<\/div>\n\n<div class=\"wp-block-column is-layout-flow wp-block-column-is-layout-flow\">\n<figure data-spectra-id=\"spectra-239f9071-5daf-49fc-b14a-d39ef3aa3a75\" class=\"wp-block-image size-full has-custom-border\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574.jpg\" width=\"800\" height=\"800\" alt=\"RTS-PDU1U-10A configurable outlet-count 1U rack PDU\" class=\"wp-image-263\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574.jpg 800w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574-300x300.jpg 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574-100x100.jpg 100w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574-600x600.jpg 600w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574-150x150.jpg 150w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/08\/11072684285_1346135574-768x768.jpg 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/figure>\n\n<h3 class=\"wp-block-heading\"><a href=\"https:\/\/ritoks.com\/products\/2-14-outlet-1u-rack-pdu-10a-250v-double-pole-switch\/\">RTS-PDU1U-10A 1U Rack PDU<\/a><\/h3>\n\n<p class=\"wp-block-paragraph\">250V, 10A, 1U family with 2\u201314 outlet-count variants.<\/p>\n<\/div>\n<\/div>\n\n<p class=\"wp-block-paragraph\">The table is intentionally conservative.<\/p>\n\n<p class=\"wp-block-paragraph\">Where data is missing, the correct sourcing step is to confirm the exact variant rather than fill the gap with assumptions.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"components-vs-assembled\">13. Modular Components Are Not the Same as an Assembled Rack PDU<\/h2>\n\n<p class=\"wp-block-paragraph\">RTS-PDUSM deserves special attention because it covers a broad range of socket and input components.<\/p>\n\n<p class=\"wp-block-paragraph\">That makes it useful for discussions involving:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>C13<\/li>\n\n\n<li>C19<\/li>\n\n\n<li>regional socket formats<\/li>\n\n\n<li>different input connector styles<\/li>\n\n\n<li>modular PDU construction<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">But it should not be used as evidence that every listed component can already be ordered as any desired assembled rack PDU.<\/p>\n\n<p class=\"wp-block-paragraph\">For example:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">C13 component available<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">does not automatically mean:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Complete RITOKS C13 rack PDU available in every outlet count and voltage.<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">Final assembly compatibility must be confirmed.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"common-mistakes\">14. Common Rack PDU Selection Mistakes<\/h2>\n\n<h3 class=\"wp-block-heading\">Choosing by Outlet Count Alone<\/h3>\n\n<p class=\"wp-block-paragraph\">More outlets do not automatically mean more usable electrical capacity.<\/p>\n\n<h3 class=\"wp-block-heading\">Mixing Up Input Plug and Output Socket<\/h3>\n\n<p class=\"wp-block-paragraph\">These are different parts of the specification and should be stated separately.<\/p>\n\n<h3 class=\"wp-block-heading\">Assuming a Socket Component Means a Complete PDU Exists<\/h3>\n\n<p class=\"wp-block-paragraph\">RTS-PDUSM is a modular component family, not evidence of every possible assembled combination.<\/p>\n\n<h3 class=\"wp-block-heading\">Assuming a 250V Socket Rating Defines the PDU Input<\/h3>\n\n<p class=\"wp-block-paragraph\">Component ratings and assembled PDU input voltage should not be treated as identical unless the exact product data confirms it.<\/p>\n\n<h3 class=\"wp-block-heading\">Assuming Every Rack PDU Is 1U or 0U<\/h3>\n\n<p class=\"wp-block-paragraph\">Rack format must be verified from the exact model.<\/p>\n\n<h3 class=\"wp-block-heading\">Calling a Master-Switch PDU a \u201cSwitched PDU\u201d<\/h3>\n\n<p class=\"wp-block-paragraph\">A local master switch is not the same as remote outlet-level switching.<\/p>\n\n<h3 class=\"wp-block-heading\">Assuming Metering or Monitoring Is Standard<\/h3>\n\n<p class=\"wp-block-paragraph\">RITOKS now publishes distinct <a href=\"https:\/\/ritoks.com\/product-category\/rack-power-distribution\/smart-rack-pdus\/\">smart rack PDU<\/a>, <a href=\"https:\/\/ritoks.com\/product-category\/rack-power-distribution\/metered-rack-pdus\/\">metered rack PDU<\/a> and <a href=\"https:\/\/ritoks.com\/product-category\/rack-power-distribution\/ats-rack-pdus\/\">ATS rack PDU<\/a> families. Compare the documented functions of the <a href=\"https:\/\/ritoks.com\/products\/p-series-smart-rack-pdu\/\">P Series Smart Rack PDU<\/a>, <a href=\"https:\/\/ritoks.com\/products\/local-display-metered-rack-pdu-16a-63a\/\">Local-Display Metered Rack PDU<\/a> and <a href=\"https:\/\/ritoks.com\/products\/la-pd-series-dual-input-ats-rack-pdu\/\">LA-PD Dual-Input ATS Rack PDU<\/a>; monitoring, local metering and automatic source transfer are separate architectures and should not be treated as interchangeable.<\/p>\n\n<h3 class=\"wp-block-heading\">Assuming \u201cSurge Protected\u201d Defines the Exact Protection Level<\/h3>\n\n<p class=\"wp-block-paragraph\">Surge performance requires exact technical parameters and supporting documentation.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"inquiry-checklist\">15. What Buyers Should Include in a Rack PDU Inquiry<\/h2>\n\n<p class=\"wp-block-paragraph\">A useful sourcing inquiry should provide the requirements already known for the project. Use the <a href=\"https:\/\/ritoks.com\/rack-pdu-rfq-checklist\/\">Rack PDU RFQ checklist<\/a> to organize them.<\/p>\n\n<p class=\"wp-block-paragraph\">Consider including:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>required input voltage<\/li>\n\n\n<li>required current<\/li>\n\n\n<li>input plug or connector<\/li>\n\n\n<li>output socket type<\/li>\n\n\n<li>outlet count<\/li>\n\n\n<li>rack format<\/li>\n\n\n<li>cord length or no-cord requirement<\/li>\n\n\n<li>quantity<\/li>\n\n\n<li>mounting constraints<\/li>\n\n\n<li>surge-protection requirement, if any<\/li>\n\n\n<li>required technical documents<\/li>\n\n\n<li>destination country<\/li>\n\n\n<li>delivery requirement<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Where a parameter has not yet been determined by the project, do not guess simply to fill the RFQ.<\/p>\n\n<p class=\"wp-block-paragraph\">For example:<\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">Input plug: To be confirmed<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">is better than choosing a plug type without knowing the upstream connection.<\/p>\n\n<h3 class=\"wp-block-heading\">Example Rack PDU Requirement Template<\/h3>\n\n<pre class=\"wp-block-preformatted\">Project \/ rack type: [project description]\nRequired voltage: [voltage]\nRequired current: [current]\nInput plug \/ connector: [required type]\nOutput sockets: [required type]\nOutlet count: [number]\nRack format: [required format]\nCord requirement: [length \/ no-cord]\nQuantity: [quantity]\nSurge requirement: [if applicable]\nRequired documents: [documents]\nDestination: [country \/ region]\nDelivery requirement: [schedule]<\/pre>\n\n<p class=\"wp-block-paragraph\">This template communicates buyer requirements.<\/p>\n\n<p class=\"wp-block-paragraph\">It does not replace the electrical design of the rack or upstream circuit.<\/p>\n\n<h2 class=\"wp-block-heading\" id=\"faq\">Frequently Asked Questions<\/h2>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>What Is the Most Important Specification When Choosing a Rack PDU?<\/summary>\n<p class=\"wp-block-paragraph\">There is no single specification that replaces the others.<\/p>\n\n\n<p class=\"wp-block-paragraph\">Voltage, current, input connection, output sockets, outlet count and physical format all need to be considered together.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>How Many Outlets Should a Rack PDU Have?<\/summary>\n<p class=\"wp-block-paragraph\">Use the outlet count required by the equipment and project plan.<\/p>\n\n\n<p class=\"wp-block-paragraph\">Current RITOKS assembled products include an 8-outlet PDU and a 1U family with 2\u201314 outlet variants.<\/p>\n\n\n<p class=\"wp-block-paragraph\">A universal spare-outlet percentage is not used in this guide.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Does RITOKS Offer C13 and C19 Rack PDUs?<\/summary>\n<p class=\"wp-block-paragraph\">Current published data confirms C13 and C19 modular socket components under RTS-PDUSM.<\/p>\n\n\n<p class=\"wp-block-paragraph\">It does not yet confirm a complete assembled RITOKS C13\/C19 rack PDU family.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Does RITOKS Offer a 1U Rack PDU?<\/summary>\n<p class=\"wp-block-paragraph\">Yes.<\/p>\n\n\n<p class=\"wp-block-paragraph\">RTS-PDU1U-10A currently publishes a 1U configuration.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Does RITOKS Offer a 0U Rack PDU?<\/summary>\n<p class=\"wp-block-paragraph\">A 0U RITOKS product is not currently confirmed in the reviewed product data.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Are RITOKS Rack PDUs Metered or Smart?<\/summary>\n<p class=\"wp-block-paragraph\">Current published rack PDU pages do not confirm metering, remote monitoring, SNMP or smart\/network functionality.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Is the RTS-PDU1U-10A a Switched PDU?<\/summary>\n<p class=\"wp-block-paragraph\">It publishes a double-pole master switch.<\/p>\n\n\n<p class=\"wp-block-paragraph\">That should not be confused with remote outlet-level switching or a managed\/switched PDU category.<\/p>\n<\/details>\n\n<details class=\"wp-block-details is-layout-flow wp-block-details-is-layout-flow\"><summary>Can Buyers Request Other Plug or Socket Options?<\/summary>\n<p class=\"wp-block-paragraph\">RTS-PDUSM publishes a broad range of modular connector and socket options.<\/p>\n\n\n<p class=\"wp-block-paragraph\">Exact compatibility with an assembled PDU configuration should be confirmed for the requested model and variant.<\/p>\n<\/details>\n\n<h2 class=\"wp-block-heading\" id=\"cta\">Need Help Matching a Rack PDU Configuration?<\/h2>\n\n<p class=\"wp-block-paragraph\">RITOKS currently publishes rack-power products covering:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>modular input and outlet components<\/li>\n\n\n<li>a fixed 125V 8-outlet assembled PDU<\/li>\n\n\n<li>a 250V 1U PDU family with multiple outlet-count options<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">When sending an inquiry, provide the electrical, connection and physical requirements already defined by the project.<\/p>\n\n<p class=\"wp-block-paragraph\"><a href=\"https:\/\/ritoks.com\/services\/\">RITOKS<\/a> can then compare those requirements with currently published product families and confirm which exact details still need verification.<\/p>\n\n<ul class=\"wp-block-list\">\n<li><a href=\"https:\/\/ritoks.com\/product-category\/rack-power-distribution\/\">View Rack Power Distribution \u2192<\/a><\/li>\n\n\n<li><a href=\"https:\/\/ritoks.com\/product-category\/rack-power-distribution\/rack-pdus-socket-modules\/\">View Rack PDUs &amp; Socket Modules \u2192<\/a><\/li>\n\n\n<li><a href=\"https:\/\/ritoks.com\/products\/modular-pdu-outlet-socket-components-c13-c19-regional-options\/\">View Modular PDU Socket Components \u2192<\/a><\/li>\n\n\n<li><a href=\"https:\/\/ritoks.com\/products\/8-outlet-us-rack-pdu-15a-125v-surge-protected-switch\/\">View the 8-Outlet 125V Rack PDU \u2192<\/a><\/li>\n\n\n<li><a href=\"https:\/\/ritoks.com\/products\/2-14-outlet-1u-rack-pdu-10a-250v-double-pole-switch\/\">View the 2\u201314 Outlet 1U Rack PDU \u2192<\/a><\/li>\n<\/ul>\n\n<div class=\"wp-block-buttons is-layout-flex wp-block-buttons-is-layout-flex\">\n<div class=\"wp-block-button\"><a class=\"wp-block-button__link has-ast-global-color-0-color has-ast-global-color-5-background-color has-text-color has-background wp-element-button\" href=\"https:\/\/ritoks.com\/contact-us\/\" style=\"border-radius:6px\">Contact RITOKS \u2192 Request a Quote<\/a><\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>Rack PDU Selection Guide: Outlet Count, Voltage, Plug and Socket Format Selecting a rack power distribution unit involves more than [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"no-sidebar","site-content-layout":"page-builder","ast-site-content-layout":"full-width-container","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"disabled","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"disabled","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":null,"ritoks_resource_product_cat_term_id":0,"footnotes":""},"categories":[67],"tags":[],"class_list":["post-734","post","type-post","status-publish","format-standard","hentry","category-rack-power-distribution"],"acf":[],"spectra_blocks_featured_image_url":null,"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/tr\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/posts\/734","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/comments?post=734"}],"version-history":[{"count":7,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/posts\/734\/revisions"}],"predecessor-version":[{"id":2408,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/posts\/734\/revisions\/2408"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/media?parent=734"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/categories?post=734"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/tr\/wp-json\/wp\/v2\/tags?post=734"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}