{"id":2910,"date":"2026-10-22T07:24:12","date_gmt":"2026-10-22T07:24:12","guid":{"rendered":"http:\/\/ritoks.com\/"},"modified":"2026-10-22T09:29:30","modified_gmt":"2026-10-22T09:29:30","slug":"pdu-meter-accuracy-low-load-conditions","status":"publish","type":"post","link":"https:\/\/ritoks.com\/vi\/pdu-meter-accuracy-low-load-conditions\/","title":{"rendered":"PDU Meter Accuracy at Low Loads: What the Test Conditions Reveal"},"content":{"rendered":"<h2 class=\"wp-block-heading\">Quick answer<\/h2>\n<p class=\"wp-block-paragraph\">PDU measurement accuracy must be read with the exact quantity, range and test conditions attached. A display showing many decimal places does not establish accuracy at low current or low power factor. Verify whether the stated error applies to the operating range and measurement level you actually need.<\/p>\n<p class=\"wp-block-paragraph\">Ask for separate specifications for current, active power, energy and power factor where relevant. Distinguish accuracy from resolution, update interval and communications polling. A register that can be read reliably may still lack the measurement-quality evidence needed for the intended decision.<\/p>\n<p class=\"wp-block-paragraph\">For a low-load comparison, define the load condition and acceptance requirement before selecting a PDU or arranging a qualified verification. Do not borrow another manufacturer&#8217;s accuracy class or treat a family description as an exact-model calibration result.<\/p>\n<h2 class=\"wp-block-heading\">Keep four data characteristics separate<\/h2>\n<p class=\"wp-block-paragraph\">Measurement accuracy, displayed resolution, update timing and retrieval timing describe different aspects of the data. They should have separate fields in the procurement checklist.<\/p>\n<figure class=\"wp-block-table\"><table>\n<thead>\n<tr>\n<th>\u0110\u1eb7c \u0111i\u1ec3m<\/th>\n<th>Question to ask<\/th>\n<th>\u0110i\u1ec1u \u0111\u00f3 kh\u00f4ng ch\u1ee9ng minh \u0111\u01b0\u1ee3c \u0111i\u1ec1u g\u00ec<\/th>\n<\/tr>\n<\/thead>\n<tbody><tr>\n<td>\u0110\u1ed9 ch\u00ednh x\u00e1c<\/td>\n<td>What error is specified for this quantity and condition?<\/td>\n<td>How many digits are displayed<\/td>\n<\/tr>\n<tr>\n<td>Resolution<\/td>\n<td>What increment can the display or field represent?<\/td>\n<td>That each displayed increment is accurate<\/td>\n<\/tr>\n<tr>\n<td>Measurement update<\/td>\n<td>How often is the measured value refreshed?<\/td>\n<td>Every network poll contains a new sample<\/td>\n<\/tr>\n<tr>\n<td>Data retrieval<\/td>\n<td>How is the quantity exposed to the management system?<\/td>\n<td>The meter&#8217;s specified measurement performance<\/td>\n<\/tr>\n<tr>\n<td>Energy accumulation<\/td>\n<td>What counter scope and interval apply?<\/td>\n<td>A snapshot is a complete period measurement<\/td>\n<\/tr>\n<\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">Raritan&#8217;s official specification for the identified PX4-5551WA-E7M26V2 lists accuracy and resolution separately for several quantities and measurement levels. That illustrates a useful specification format: the quantity and resolution do not replace the accuracy information. Its figures are not assigned to any RITOKS family here. <a href=\"https:\/\/cdn.raritan.com\/product-selector\/pdus\/PX4-5551WA-E7M26V2\/PX4-5551WA-E7M26V2-spec.pdf\" target=\"_blank\" rel=\"noopener\">Raritan, <em>PX4-5551WA-E7M26V2 technical specifications<\/em><\/a>.<\/p>\n<p class=\"wp-block-paragraph\">Copy the relevant qualifiers when preparing a purchasing requirement. A shortened description such as \u201caccurate digital metering\u201d gives the supplier little information about the operating condition you need to evaluate.<\/p>\n<figure data-spectra-id=\"spectra-feb3e8bf-c2b1-4699-b4cc-0b9f6f004701\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01.webp\" alt=\"Four separate definitions for accuracy, resolution, update and retrieval\" class=\"wp-image-2908\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-01-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">These data characteristics address different questions; no model-specific error limit or timing is assigned.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">Start with the quantity and measurement level<\/h2>\n<p class=\"wp-block-paragraph\">Current, active <a href=\"https:\/\/ritoks.com\/vi\/kw-vs-kwh-energy-meter-readings\/\">power and energy<\/a> are not interchangeable quantities. A current-accuracy statement should not automatically become an active-power or energy-accuracy claim. A displayed power factor also needs its own definition and applicable conditions.<\/p>\n<p class=\"wp-block-paragraph\">Identify whether the specification belongs to the inlet, branch or individual outlet. One measurement level&#8217;s error statement may not establish another level&#8217;s performance. The required data should match the actual equipment comparison or operational task.<\/p>\n<p class=\"wp-block-paragraph\">A total-rack measurement can be useful for rack planning while being insufficient for comparing small individual loads. A per-outlet architecture can address that granularity requirement, but it still needs suitable exact-model accuracy evidence. More detailed data are not automatically more accurate data.<\/p>\n<p class=\"wp-block-paragraph\">Also retain the measurement units and interpretation. A field labelled load may not be the same quantity as active power or accumulated energy. Obtain the data definition instead of treating an informal interface label as a complete specification.<\/p>\n<h2 class=\"wp-block-heading\">Ask which part of the range is covered<\/h2>\n<p class=\"wp-block-paragraph\">For a low-load use case, request the specified operating range and any minimum condition behind the accuracy claim. A statement that describes one part of the meter&#8217;s range should not be extended to a condition outside that scope.<\/p>\n<p class=\"wp-block-paragraph\">Ask how the error is expressed. The exact specification may refer to the reading, range or another defined basis. These descriptions can have different implications for small measured values, so preserve the original form rather than replace it with an unsupported percentage shorthand.<\/p>\n<p class=\"wp-block-paragraph\">The review should identify the current, voltage and load conditions relevant to the proposed task. If an accuracy condition includes a power-factor range or another qualification, compare it with the intended load. A claim tested under one condition does not automatically establish the required result under another.<\/p>\n<p class=\"wp-block-paragraph\">Do not invent an acceptable lower-current boundary from the PDU&#8217;s maximum rating. Likewise, do not assume a product becomes accurate merely because a value appears nonzero on its screen. The manufacturer needs to state the applicable measurement conditions or provide suitable supporting evidence.<\/p>\n<h2 class=\"wp-block-heading\">Preserve power-factor and operating conditions<\/h2>\n<p class=\"wp-block-paragraph\">Low power and low current are related but not identical descriptions. The procurement question should identify the relevant quantity and operating state instead of use \u201csmall load\u201d as the only condition.<\/p>\n<p class=\"wp-block-paragraph\">If the application includes varying or nonlinear loads, describe them in the requirement and request the applicable measurement scope. Do not infer coverage of every waveform from a general digital-meter label. Exact documentation determines what conditions the manufacturer supports.<\/p>\n<p class=\"wp-block-paragraph\">Record the environmental and installation conditions attached to the specification where relevant. A comparison made under conditions different from the stated basis needs an explanation and appropriate qualified review. Do not silently call it a calibration failure or a pass.<\/p>\n<p class=\"wp-block-paragraph\">The purpose is to make the evidence fit the decision. A simple trend-monitoring task and a close comparison between two small equipment loads can require different quality objectives. State what difference the report must meaningfully distinguish before asking for a generic accuracy claim.<\/p>\n<h2 class=\"wp-block-heading\">What the RITOKS PDU pages establish<\/h2>\n<p class=\"wp-block-paragraph\">C\u00e1i <a href=\"https:\/\/ritoks.com\/vi\/products\/monitored-pdu-5-0-with-outlet-level-metering\/\">Monitored PDU 5.0 family<\/a> identifies outlet-level energy monitoring without outlet switching. Its public description does not provide the complete low-load accuracy conditions or a model-specific calibration record.<\/p>\n<p class=\"wp-block-paragraph\">C\u00e1i <a href=\"https:\/\/ritoks.com\/vi\/products\/p-series-smart-rack-pdu\/\">P Series smart rack PDU family<\/a> distinguishes aggregate monitoring from per-outlet monitoring across its platforms. Select the measurement level independently from switching functions, electrical configuration and interface options.<\/p>\n<p class=\"wp-block-paragraph\">C\u00e1i <a href=\"https:\/\/ritoks.com\/vi\/products\/local-display-metered-rack-pdu-16a-63a\/\">local-display metered rack PDU page<\/a> explicitly leaves measurement accuracy subject to supplier confirmation. Its documented voltage, current and load display should not be expanded into an unverified per-outlet accuracy or energy specification.<\/p>\n<p class=\"wp-block-paragraph\">For an enquiry, send the required quantity, measurement level, expected load condition and intended use. Request the exact orderable model&#8217;s accuracy expression, range, resolution and relevant test conditions. A protocol request alone does not communicate the low-load measurement requirement.<\/p>\n<h2 class=\"wp-block-heading\">Design a qualified comparison before calling it a test<\/h2>\n<p class=\"wp-block-paragraph\">A comparison record should identify the reference instrument, its applicable verification basis, the measured quantity and the equipment state. Merely placing two displays side by side does not establish which one is correct or whether their boundaries match.<\/p>\n<p class=\"wp-block-paragraph\">Define the acceptance criterion before collecting results. It should follow the applicable product specification and project requirement, with the responsible reviewer accounting for the reference measurement&#8217;s limitations. This guide assigns no universal error threshold or calibration procedure.<\/p>\n<p class=\"wp-block-paragraph\">Align the readings in time and scope. Values from different operating states or different connection points may not be directly comparable. If the PDU updates slowly or a management platform averages values, record that behavior rather than treat an instantaneous reference reading as an exact match.<\/p>\n<p class=\"wp-block-paragraph\">Measurements on rack power circuits require qualified personnel and an approved procedure. Do not introduce an improvised load or access live conductors to complete a comparison table. A safe, suitable method must be established for the actual installation.<\/p>\n<h2 class=\"wp-block-heading\">Use a conditional low-load review example<\/h2>\n<p class=\"wp-block-paragraph\">Consider a fictional team comparing two lightly loaded devices. The proposed PDU has per-outlet data, and its screen shows detailed current values. The quotation contains no accuracy range or power-factor condition for the intended operating point.<\/p>\n<p class=\"wp-block-paragraph\">The available evidence establishes granularity and display capability, not the quality of the intended comparison. The reviewer should request the exact measurement specification and determine whether the expected load falls within its conditions. If it does, a qualified verification plan can be prepared when required.<\/p>\n<p class=\"wp-block-paragraph\">If the condition is not covered or the information remains missing, the comparison should be reported as unsupported for that precision objective. It may still be useful for a different, explicitly limited operational purpose. This example establishes no accuracy result for a RITOKS model and does not recommend a live test method.<\/p>\n<h2 class=\"wp-block-heading\">Build the metering-quality requirement sheet<\/h2>\n<figure class=\"wp-block-table\"><table>\n<thead>\n<tr>\n<th>Requirement item<\/th>\n<th>Detail to record<\/th>\n<th>Review question<\/th>\n<\/tr>\n<\/thead>\n<tbody><tr>\n<td>Intended decision<\/td>\n<td>Trend, comparison or other reviewed use<\/td>\n<td>What difference must the data support?<\/td>\n<\/tr>\n<tr>\n<td>S\u1ed1 l\u01b0\u1ee3ng<\/td>\n<td>Current, active power, energy or other defined field<\/td>\n<td>Is the correct specification requested?<\/td>\n<\/tr>\n<tr>\n<td>Measurement boundary<\/td>\n<td>Input, branch or outlet<\/td>\n<td>Does the reading cover the required load?<\/td>\n<\/tr>\n<tr>\n<td>Operating condition<\/td>\n<td>Relevant range and load description<\/td>\n<td>Is it within the stated scope?<\/td>\n<\/tr>\n<tr>\n<td>Accuracy expression<\/td>\n<td>Exact error basis and conditions<\/td>\n<td>Were qualifiers preserved?<\/td>\n<\/tr>\n<tr>\n<td>Resolution and timing<\/td>\n<td>Display increment, update and retrieval behavior<\/td>\n<td>Are these being confused with accuracy?<\/td>\n<\/tr>\n<tr>\n<td>Verification basis<\/td>\n<td>Applicable report or qualified comparison<\/td>\n<td>Does the evidence match the model and condition?<\/td>\n<\/tr>\n<tr>\n<td>Limitation<\/td>\n<td>Missing range or condition<\/td>\n<td>What cannot yet be claimed?<\/td>\n<\/tr>\n<\/tbody><\/table><\/figure>\n<p class=\"wp-block-paragraph\">Keep this sheet with the selected PDU configuration and management-field definitions. A firmware change, model substitution or altered reporting method may require checking whether the original comparison remains applicable.<\/p>\n<p class=\"wp-block-paragraph\">A final report should separate observed values from the conclusion about their suitability. A plausible number is not itself proof of accuracy; a missing specification is not automatically proof of poor performance. Record the actual evidence and the decision it supports.<\/p>\n<p class=\"wp-block-paragraph\">Keep raw observations available where a comparison was actually performed. A rounded dashboard export can conceal the original resolution, and an average can conceal the interval used to calculate it. The retained record should identify which representation was evaluated. If a report combines several data sources, name each source and its measurement boundary instead of presenting the merged result as one instrument reading. These details allow another reviewer to understand the conclusion without repeating the work solely because the original evidence was summarized too aggressively.<\/p>\n<figure data-spectra-id=\"spectra-9b9b56c7-ab5e-475c-8694-2f2cd9e44234\" class=\"wp-block-image size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1400\" height=\"1050\" src=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02.webp\" alt=\"Matrix matching required and documented quantity, measurement level and operating conditions\" class=\"wp-image-2909\" srcset=\"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02.webp 1400w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02-300x225.webp 300w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02-1024x768.webp 1024w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02-768x576.webp 768w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02-16x12.webp 16w, https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-body-02-600x450.webp 600w\" sizes=\"auto, (max-width: 1400px) 100vw, 1400px\" \/><figcaption class=\"wp-element-caption\">A requirement-review matrix, not a calibration record or universal tolerance.<\/figcaption><\/figure>\n<h2 class=\"wp-block-heading\">C\u00e2u h\u1ecfi th\u01b0\u1eddng g\u1eb7p<\/h2>\n<h3 class=\"wp-block-heading\">Do more displayed digits mean better accuracy?<\/h3>\n<p class=\"wp-block-paragraph\">No. Resolution and accuracy are different characteristics. Request the exact error specification and its conditions.<\/p>\n<h3 class=\"wp-block-heading\">Does current accuracy establish energy accuracy?<\/h3>\n<p class=\"wp-block-paragraph\">Not automatically. Ask for the quantity you need and its applicable measurement-level specification rather than transfer a statement from another field.<\/p>\n<h3 class=\"wp-block-heading\">Does network polling prove a fresh measurement?<\/h3>\n<p class=\"wp-block-paragraph\">No. Retrieval and measurement-update timing are different. Confirm the field definition and refresh behavior for the exact model and interface.<\/p>\n<h3 class=\"wp-block-heading\">Are RITOKS low-load accuracy values published here?<\/h3>\n<p class=\"wp-block-paragraph\">No exact values are assigned in this guide. Obtain model-specific range and test conditions before approving a precision objective.<\/p>\n<h2 class=\"wp-block-heading\">T\u00e0i li\u1ec7u tham kh\u1ea3o<\/h2>\n<ul class=\"wp-block-list\">\n<li>Raritan. (2025, October 23). <em>PX4-5551WA-E7M26V2 technical specifications<\/em>. Accuracy and resolution table. Retrieved October 3, 2026. <a href=\"https:\/\/cdn.raritan.com\/product-selector\/pdus\/PX4-5551WA-E7M26V2\/PX4-5551WA-E7M26V2-spec.pdf\" target=\"_blank\" rel=\"noopener\">https:\/\/cdn.raritan.com\/product-selector\/pdus\/PX4-5551WA-E7M26V2\/PX4-5551WA-E7M26V2-spec.pdf<\/a><\/li>\n<li>RITOKS. (n.d.). <em>Monitored PDU 5.0 with outlet-level metering<\/em>. Checked October 3, 2026. <a href=\"https:\/\/ritoks.com\/vi\/products\/monitored-pdu-5-0-with-outlet-level-metering\/\">https:\/\/ritoks.com\/products\/monitored-pdu-5-0-with-outlet-level-metering\/<\/a><\/li>\n<li>RITOKS. (n.d.). <em>P Series smart rack PDU<\/em>. Checked October 3, 2026. <a href=\"https:\/\/ritoks.com\/vi\/products\/p-series-smart-rack-pdu\/\">https:\/\/ritoks.com\/products\/p-series-smart-rack-pdu\/<\/a><\/li>\n<li>RITOKS. (n.d.). <em>PDU gi\u00e1 \u0111\u1ee1 c\u00f3 \u0111\u1ed3ng h\u1ed3 \u0111o hi\u1ec3n th\u1ecb t\u1ea1i ch\u1ed7<\/em>. Checked October 3, 2026. <a href=\"https:\/\/ritoks.com\/vi\/products\/local-display-metered-rack-pdu-16a-63a\/\">https:\/\/ritoks.com\/products\/local-display-metered-rack-pdu-16a-63a\/<\/a><\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>Separate accuracy, resolution and update timing, then match the exact measurement specification to the intended low-load decision.<\/p>","protected":false},"author":1,"featured_media":2907,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"default","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ritoks_resource_detail_renderer":"viox","ritoks_resource_product_cat_term_id":105,"footnotes":""},"categories":[67],"tags":[],"class_list":["post-2910","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-rack-power-distribution"],"acf":[],"spectra_blocks_featured_image_url":{"thumbnail":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-hero-01-150x150.webp","width":150,"height":150},"medium":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-hero-01-300x169.webp","width":300,"height":169},"medium_large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-hero-01-768x432.webp","width":768,"height":432},"large":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-hero-01-1024x576.webp","width":1024,"height":576},"full":{"url":"https:\/\/ritoks.com\/wp-content\/uploads\/2026\/10\/pdu-meter-accuracy-low-load-conditions-hero-01.webp","width":1600,"height":900}},"spectra_blocks_author_info":{"display_name":"RITOKS","avatar_url":"https:\/\/secure.gravatar.com\/avatar\/6d7d0fc73468198f994ab13ef6eb6558c53b6ed1ad86364d5165efe8bdf8eb4a?s=96&d=mm&r=g","author_link":"https:\/\/ritoks.com\/vi\/author\/dazzlingwqbgmail-com\/","description":""},"_links":{"self":[{"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/posts\/2910","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/comments?post=2910"}],"version-history":[{"count":2,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/posts\/2910\/revisions"}],"predecessor-version":[{"id":2940,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/posts\/2910\/revisions\/2940"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/media\/2907"}],"wp:attachment":[{"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/media?parent=2910"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/categories?post=2910"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/ritoks.com\/vi\/wp-json\/wp\/v2\/tags?post=2910"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}