Star-Delta Overload Relay Settings Depend on Where the Relay Is Connected

Conceptual technical illustration of a three-contactor star-delta starter with a thermal relay and motor winding diagram on a service bench.

Quick answer

A star-delta overload relay must be set from the current that actually passes through its sensing elements in the selected starter connection. The same motor can require a different relay scale factor when the relay sits in the line conductors rather than in the phase windings, so copying a setting from another starter is unsafe.

Start with the LK1 starter drawing and the actual conductor route through the ZS3RU relay. Compare line current, winding current during delta operation and the relay manufacturer instruction. The motor nameplate, duty and starting method provide the design current; the drawing establishes what the relay sees. All three must agree before the dial or setting is approved.

Find the relay on the actual circuit

The overload relay is a current sensor first. Its setting only has meaning when the circuit through its poles is known. In a star-delta starter, the main contactor, delta contactor, star contactor and thermal relay can be arranged in more than one documented pattern. The drawing supplied for the selected assembly is the reference for which pattern applies.

Trace each relay terminal to its upstream and downstream connection. Does the relay carry the current supplied from the line, the current through a motor winding, or a combination created by the contactor states? Mark all three operating states: stopped, star starting and delta running. A wire that bypasses the relay in one state changes the effective sensing relationship.

Photograph the installed panel before wiring obscures the route, and label the relay terminals in the as-built record. The photo supports the drawing comparison; it does not replace the drawing. If the as-built route differs, stop the setting review and resolve the configuration.

A generic statement that a thermal relay protects a motor does not identify its location. The relevant question is narrower: which current does this relay measure while the motor is in the operating state that the setting is intended to protect?

Line and winding current are not arbitrary percentages

In a balanced three-phase motor, line and winding currents have a defined relationship for a given winding connection. They are still different quantities, and the relay sensing path decides which one it receives. The designer must use the relationship that corresponds to the actual circuit state rather than applying a remembered multiplier to every starter.

For a balanced three-phase load, the mathematical relationship between line and phase quantities follows how the windings are connected. A motor winding supplied in delta presents a different relationship from the same winding supplied in star. The overload relay is normally expected to protect the running duty, so the review must focus on the delta state unless the starter documentation establishes another method.

A multiplier is not a universal license to change a setting. It is an intermediate calculation that must connect the desired overload protection to the current seen by the relay. The temperature environment, relay class, motor service factor, ambient compensation and manufacturer instruction remain part of the selection record.

Use the exact values from the motor record and starter drawing. A nameplate current copied from the wrong winding connection, or a line current treated as a phase current, can shift the result by a large factor even when the arithmetic looks clean.

Conceptual comparison shows a relay in a line conductor versus a relay in a winding path, with distinct current labels.
Conceptual location comparison. The diagram does not assign a setting or reproduce a particular LK1 drawing.

Establish the protected running state

The relay setting should protect the motor during its intended continuous running condition and its credible overloads. For a star-delta starter, the transition from star to delta normally changes both the current path and the current magnitude. The relay may be in the circuit during starting, running or both, depending on the diagram.

Record the rated operating current at the motor's rated voltage and frequency, the winding connection used for that rating, and the expected load duty. If the machine operates below nameplate load for long periods, the designer may choose a setting based on the actual duty and the motor instructions. A purchasing agent should not simplify that decision into a fixed percentage.

Check whether the relay includes phase-loss protection, ambient compensation or a manual reset that affects the intended response. Those features do not change the physical sensing location, but they affect how the installation is set and tested. Preserve the exact ZS3RU variant and its adjustment band.

Make a state table with Star and Delta columns. In each column record contactor positions, expected line current, expected winding current, the current through the relay and the conductor that bypasses it. The table exposes mismatches before someone turns a dial.

A worked ratio example without assuming a product setting

Consider a hypothetical balanced motor whose delta running condition gives a line current of 42 A and a related winding current of about 24.25 A under the simplified balanced relationship. These are illustrative values, not data for a listed motor. The correct relay calculation depends on which of those currents pass through its sensing elements.

If the relay is placed so that it measures the winding current, a setting derived from the line-current record cannot be copied directly. The two quantities occupy different scales. If the relay measures line current, the winding value may be useful only for verifying the drawing and the protective objective. The starter diagram decides which case exists.

Write the formula and units next to the result: relay-sensed current, desired protection reference and the connection basis. Show any rounding separately from the selected adjustment-band step. A calculated 24.25 A means little if the relay band or dial increment cannot represent it exactly; choose a documented setting and explain the rounding.

The example also shows why a label such as "set to motor current" is incomplete. The installer needs to know which quantity was on the motor record and which quantity the relay receives. Without that link, the same sentence can produce two different settings.

Check the transition and short-time duty

The star period is usually short, but it still closes contacts and carries current. The relay location may cause it to see starting current only for a defined time. Confirm that the selected relay and starter sequence are intended for the motor start duration. A protective device being present does not prove that the timing and duty suit a long or frequent start.

The timer controls the change from star to delta. Its setting and the interlocking of star and delta contactors belong to the starter design. If both states can close at the same time, the electrical configuration is wrong even if the overload dial is perfect. Review the drawing for transition logic and the as-built wiring for the same condition.

Repeated starts can heat the motor and relay. A relay selected for continuous running may accumulate heat differently after several closely spaced starts. Follow the manufacturer's ambient and derating information and the motor's permitted starting duty. Do not infer an unlimited start count from the presence of a thermal element.

The test record can include a no-load functional transition and a current reading, subject to the site's approved procedure. Do not create a live fault test to prove the dial. Use the project's verification scope and the relay instructions.

Use an as-built setting register

FieldRecordWhy it matters
Motor identityNameplate, winding connection and rated currentDefines the reference current
Starter drawingLK1 drawing revision and contactor arrangementDefines current paths
Relay locationTerminals and conductors passing through ZS3RUDefines sensed quantity
Running stateDelta contactor closed, line and winding valuesConnects protection to operating duty
Setting decisionCalculation, band, rounding and approvalMakes installation repeatable

The register should be filled before the dial is finalized. A change in motor, contactor route or relay model reopens the relevant rows. This is particularly important when a standard starter is adapted to a different motor without changing the mechanical enclosure.

Include the date and person who approved the setting, using a real project role rather than an invented engineer title. The technical reader can then distinguish supplier data from the installed decision.

A photograph of the relay dial without the drawing and conductor route is not a setting record. It shows one position while hiding whether the device measures the intended current.

Conceptual state table contrasts stopped, star and delta states by contactor position and relay path.
Conceptual state comparison only; the actual contact schedule belongs to the selected starter drawing.

Common mistakes that survive a visual check

One mistake is assuming every star-delta overload is placed in the same location because the enclosure looks the same. Another is using the motor nameplate current without checking whether the starter drawing expects winding current. A third is changing the relay band to match a replacement motor without revisiting the contactor sequence.

A technician may also copy a setting from a nearby panel that drives a different motor. Even identical model plates can hide a different tap voltage, winding or load profile. Use the equipment identifier, not the panel location, as the primary key.

The overload relay should not be used to compensate for an undersized starter or a faulty contactor. If the current is abnormal because a contact is not closing, the correct response is to find the circuit fault. Repeatedly increasing the setting would defeat the protective function.

Keep rejected settings with a reason in the commissioning file if the team compared them. That makes a later audit faster and prevents a remembered percentage from being treated as universal evidence.

What to send with a star-delta starter inquiry

For the LK1 star-delta motor starter assembly family, supply the motor output, voltage, frequency, rated current, winding terminals and intended starting duty. State whether the panel uses line or winding sensing and attach the current starter drawing. Ask for the assembly drawing that corresponds to the requested arrangement.

For the ZS3RU thermal overload relay family, request the exact adjustment band and the installation instruction for the selected variant. Confirm the relay location and the setting basis in the same response. A family range from 0.11 A to 100 A is too broad to approve a particular setting.

A useful quotation identifies the motor, contactor layout, relay and setting relationship. A quoted relay without the starter context can still be the wrong choice for the installation.

When the source information is incomplete, mark the setting as pending rather than choosing a plausible value. The rest of the panel can proceed while the exact motor and starter records are obtained.

Acceptance rule

The overload setting passes review when the motor reference current, winding connection and relay sensing path form one consistent circuit, and the selected ZS3RU band can realize the approved value. The transition logic must also be documented and the as-built conductor route must match the drawing.

This produces a setting that another technician can verify from the file. It also separates the engineering question from the purchasing question: first confirm what the relay sees, then select and set the device that can measure it reliably.