Electrical Measurement & Monitoring · Technical Explainer
Measurement Device RFQ: Range, Output, Supply and Isolation
“Current sensor required” is rarely enough for an industrial RFQ. A current transformer, Hall-effect sensor, resistive shunt and finished current transducer can all help measure current, but they do not share the same input waveform, output signal, supply or installation method. A buyer needs to describe the actual measurement task before naming a family. The purpose of this guide is to make the technical request precise enough for a supplier to propose one documented device without silently crossing technology boundaries.

RITOKS lists Current Transformers, Hall Current Sensors, Current Shunts, and separate AC and DC current transducers. Those are distinct product families, not alternate names for the same component. The RFQ should state the electrical function first, then request exact-model evidence for the chosen family.
| First question | Why it matters | Example evidence |
|---|---|---|
| AC, DC or both? | Conventional CTs need changing flux; other architectures differ | Exact waveform scope |
| What current range? | Nominal, low-end and maximum conditions differ | Model input/range table |
| What receiver input? | /5 A, millivolt, analog voltage and mA are not interchangeable | Meter/PLC manual |
| What supply? | Some sensors/transducers are powered; a shunt is resistive | Exact supply specification |
| What separation? | Isolation requirement depends on boundary and system | Exact barrier/rating document |
This table screens architectures only. It is not a recommendation for a particular circuit.
Start With the Waveform and Current Path
Write whether the measured current is steady DC, alternating AC, bidirectional DC, pulsed, or AC with a DC component. Include normal operating range, useful low-end resolution, maximum expected current and relevant transient conditions. An ordinary electromagnetic CT cannot measure steady DC. Schneider Electric's CT explanation gives the changing-flux reason. A Hall sensor can be designed for AC and DC, but the selected model's documentation controls its actual limits.
Then show where the sensor would go: a conductor through an aperture, a shunt inserted into a power path, a small current entering transducer terminals, or an existing CT secondary feeding a conditioning device. These are physically different inputs. A data sheet that says “0–5 A input” cannot be treated as if it senses a 500 A busbar through a window. Provide a simple system diagram or photo that clearly identifies the current path, while leaving installation approval to the engineer.
Do not use the desired controller output to guess the sensing method. A PLC may prefer 4–20 mA, but a raw shunt or CT does not necessarily produce that signal. An additional documented conditioner could be designed, or a finished transducer may be selected. Those options must be identified as separate architectures and costed separately.
Keep CT, Hall and Shunt Questions Separate
For a CT, ask for rated primary and secondary, frequency, accuracy class, burden, physical opening or split-core form, insulation and installation instructions. The RITOKS BH-0.66 60I CT has documented /5 A examples, while the GTA20L miniature CT has 20 mA AC output in its listed models. Neither output should be generalized to every CT in the category.
For a Hall route, ask for nominal primary current and measuring range separately, supply, output transfer, opening, offset and response. The published HS2V H02 family lists AC/DC/pulsed measurement, ±15 V DC supply and ±4 V analog output at nominal primary current. That voltage output is not a CT secondary or a 4–20 mA loop. Its range varies by exact model.
For a resistive shunt, ask for rated current, rated millivolt output, terminal arrangement, thermal duty and compatible meter. The FL-2-75 family has 75 mV rated-output options tied to selected rated currents. A shunt is conductive in the measured path; it must not be called a galvanically isolated aperture sensor. Each of these families needs a different safety and installation review.

Treat Finished Transducers as Their Own Family
A finished current transducer converts a defined measured input into a defined standardized signal. It may incorporate sensing and conditioning, but its exact input topology still matters. RITOKS publishes the VDT-26 AC current transducer through the AC category and the WBI334U01-S DC current transducer in the DC category. Do not use the DC model for an AC requirement or infer the AC model's output from the DC model.
The WBI334U01-S public page describes zero-to-positive DC input choices, 0–20 mA or 4–20 mA outputs and 12 V or 24 V DC supply options. Those fields belong to that specific family. A project requiring bidirectional battery current, a high-current busbar aperture or an analog-voltage output must be stated openly. The supplier should either document another exact model or mark the requirement unsupported; no invented option should be added to the published WBI product.
An AC current transducer may have its own input arrangement, such as direct AC current terminals or a CT-related input, depending on exact model. The category description alone does not tell the installer which wiring applies. Request its full data sheet and terminal drawing before quoting a supposedly compatible model.
Output Is a Receiver Contract
The measurement device and receiving meter or PLC must agree on electrical signal and scaling. A 5 A CT input, a 20 mA CT secondary, a 75 mV shunt input, ±4 V Hall output and 4–20 mA transducer signal are five different interfaces. A controller may support several through different cards, but an “analog input” label does not prove the installed channel accepts them all. State the receiver model, channel, supported range and desired engineering units.
Some buyers want a standard 4–20 mA signal because it works with an existing control architecture. Phoenix Contact's signal-conditioning guide shows how a conditioner can convert one standard signal to another when explicitly specified. That does not make a raw CT or shunt a 4–20 mA source. Every conditioning stage adds its own supply, load, accuracy and isolation questions.
Write down the expected transfer: what primary current corresponds to the low and high output endpoints, whether current can reverse, and what happens outside the normal range. The manufacturer's exact data sheet and receiver configuration must support the mapping. Without them, a sensor may electrically connect but report an incorrect value.
Supply and Isolation Are Not Optional Footnotes
A CT secondary is not described by the same auxiliary-power field as an active Hall device. The HS2V H02 requires its published ±15 V DC supply. WBI334U01-S lists 12 V or 24 V DC options. A resistive shunt does not have a powered sensor output, although its receiving electronics may need power. Put the supply requirement against the specific family rather than adding a generic 24 V line to every device.
Isolation must identify the boundary being discussed. A Hall aperture, a CT magnetic coupling, a transducer's internal barrier and an isolated receiver input are different components of a system. An assertion that “the measurement is isolated” must be supported by the exact model's insulation documentation and the circuit design. National Instruments' isolation overview distinguishes ground-loop and common-mode benefits from the safety purposes of isolation. No one product-category name establishes whole-system safety.
If a shunt sits at a potential different from the PLC ground, the millivolt receiver or conditioner may need a documented common-mode and isolation capability. If a CT secondary is selected, its burden and open-secondary safety instructions matter. If a Hall sensor is chosen, its supply and analog ground need review. Each architecture has a different checklist; a merged “current sensor isolation” line is too vague.
Physical Fit and Maintenance Shape the Choice
Provide conductor diameter or busbar shape, available aperture, mounting orientation, panel space, cable exit and service access. A split-core CT can be useful where an existing conductor should not be disconnected, but its core closure, exact opening and output still need documentation. A shunt requires a conductive insertion point and thermal design. A DIN-rail transducer consumes rail and terminal space. A Hall sensor may need separate supply wiring and a conductor opening.
Also state environmental conditions: ambient temperature, vibration, moisture, contamination and service access. Do not infer an IP rating or lifetime from the shape of an enclosure. If a proposed device's public page omits required environmental data, request the exact datasheet rather than importing another model's value. The complete measurement chain should remain inspectable and maintainable without treating a blog as an installation manual.
The Cross-Family RFQ Packet
Send one project brief, but separate the family-specific appendices:
- State waveform, direction, nominal and maximum current, useful low-end resolution and monitoring purpose.
- Provide circuit location, conductor or input-terminal arrangement, drawing and available mounting space.
- Name the receiver and its exact input range, scaling, reference, isolation and alarm behavior.
- State available sensor supply, if relevant, and the required output signal.
- Define the isolation boundary and applicable documentation requirement.
- For CTs, request ratio, secondary, burden and installation instructions; for Hall, supply and transfer; for shunts, rated millivolt output and terminals; for finished transducers, input/output/supply pairing.
- Ask for exact model, quantity, destination, complete datasheet and unresolved exceptions.

Do not ask a supplier to fill every architecture into one comparison cell. The right result may be that several families are excluded immediately by waveform, receiver or physical fit. Record that exclusion in the RFQ so the next reviewer understands why the selected product was proposed.
Selection Summary
A measurement RFQ becomes useful when range, output, supply, isolation and physical current path are independent fields. The RITOKS Electrical Measurement & Monitoring range provides different CT, Hall, shunt and transducer branches. Use each published page only for its own model's evidence. Send the brief through RITOKS contact and ask the supplier to mark unsupported fields rather than assuming interchangeability among architectures.
Source notes
- RITOKS CTs, Hall sensors, shunts, AC transducers and DC transducers: separate published family ownership.
- Schneider Electric CT explanation: changing-flux AC measurement principle.
- Phoenix Contact signal conditioning: separate conversion stage when interfaces differ.
- NI isolation technology: barrier and measurement-system context.